FOR 15220A AND 15240A FIRE ALARM CONTROL PANELS
Compatible 4-Wire Smoke Detectors must have a minimum absolute voltage range of 19 to 28 V.D.C.
DECTECTOR
MANUFACTURER
W/BASE
DETECTOR
ORDER NO.
W/BASE
SYSTEM SENSOR, DIV. of PITWAY CORP.
9377
1424
9378
2424
9779
2424TH
9337
1112/24
9338
2112/24
9339
2112/24T
9340
2112/24TSRB
9358 W/9362
1451 W/B402B
9359 W/9362
2451 W/B402B
9360 W/9362
2451TH W/B402B
9447 W/9362
5451 W/B402B
9421 W/9362
4451HT W/B402B
9440
DH1851DC
9437
DH2851DC
9164
DH400ACDCI
9165
DH400ACDCP
9175
6424
NOTE: For specific wiring and installation information read the instructions provided with each device.
COMPATIBLE 4-WIRE SMOKE DETECTORS
MAXIMUM
STANDBY
CURRENT
0.100ma.
0.120ma.
0.120ma.
0.050ma.
0.050ma.
0.050ma.
15ma.
0.120ma.
0.120ma.
0.120ma.
0.120ma.
0.120ma.
0.120ma.
0.120ma.
25ma.
25ma.
10ma.
III- 20
firealarmresources.com
(Cont'd)
MAXIMUM
ALARM
CURRENT
NOTES
41ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
25ma.
MUST USE EOL RELAY
25ma.
MUST USE EOL RELAY
25ma.
MUST USE EOL RELAY
45ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
39ma.
MUST USE EOL RELAY
39ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
41ma.
MUST USE EOL RELAY
100ma.
MUST USE 6 WIRES
100ma.
MUST USE 6 WIRES
10ma.
MUST USE EOL RELAY
AND 6 WIRES