4.4.9

Calculating Current Draw and Standby Battery

This section helps you determine the current draw and standby battery needs for your installation (18
Ampere Hours max. will fit in cabinet). Complete the remaining instructions in Table 4-3.
Batteries larger than 18 AH will not fit in the main control cabinet, and must be housed in the RBB
Accessory Battery Cabinet. Maximum of 33 Amp Hours per system.
Device
ECS-50W 25V
ECS-50W 70.7V
ECS-CE4
A
Notification Devices
B
C Total current rating of all devices in system (Line B) X 0.001
D Number of standby hours (24 or 60 for NFPA 72)
E Multiply line C (standby current) and D:Total standby AH
F Alarm sounding period in hours (For example, 5 minutes = 0.0833 hours):
G Multiply line C (alarm current) and F:Total alarm AH
H Add lines E and G (AH = Ampere Hours):Total AH required
4.5

Installing the ECS-INT50W

This section provides information on how to install the ECS-INT50W for use with the ECS-Series
products.The ECS-INT50W Internal Amplifier can fit inside the IFP-300ECS or IFP-2000ECS cabinet.
It can also be adapted to fit into the ECS-2100ECS cabinet with the ECS-AMPMT mounting kit (sold
separately). It is used to amplify the audio message for distribution throughout the facility for the
Emergency Communication System.
4.5.1
Board Layout & Mounting
IN1 / OUT1
Table 4-3: Current Draw ECS-50W and ECS-CE4
No. of
Devices
1
1
0 or 1
Refer to device manual for number of devices and current ratings.
Figure 4-33 Front View of ECS-INT50W
4-24
Current Per Device
Standby:
85 mA
Alarm:
525 mA
Standby:
100 mA
Alarm:
580 mA
Standby:
20 mA
Alarm (All Channels):
180 mA
Current Subtotals:
Current Subtotals:
151455
Standby
Alarm
Current
Current
85 mA
525 mA
100 mA
580 mA
20mA
180 mA
mA
mA
mA
mA
A
A
H
AH
H
AH
AH
VBUS
SBUS
Power
DIP Switch