ECS Device Installation
4.8

Installing the ECS-DUAL50W or ECS-DUAL-50WB

This section provides information on how to install the ECS-DUAL50W for use with the IFP-2100ECS,
IFP-2000ECS, IFP-1000ECS, IFP-300ECS and IFP-100ECS. ECS-DUAL50W is available in a black
cabinet as P/N ECS-DUAL50WB.*
4.8.1

ECS-DUAL50W Board Layout

Figure 4-56 shows the location of terminals, DIP switch's and Expander connection used in the
installation of the ECS-DUAL50W.
* All references to ECS-DUAL50W within this manual are applicable to the ECS-DUAL50WB.
4.8.2

Mounting the ECS-DUAL50W

The ECS-DUAL50W is equipped with a separate enclosure. It is also available in a black cabinet.
(ECS-DUAL50WB) Refer to Section 3.1 when selecting a mounting location for the ECS-DUAL50W.
The panel should be accessible to main drop wiring runs. It should be mounted as close to the center
of the building as possible and located within a secured area, but should be accessible for testing and
service.
Mount the control panel cabinet so it is firmly secured to the wall surface. When mounting on concrete,
especially when moisture is expected, attach a piece of ¾" plywood to the concrete surface and then
attach the cabinet to the plywood. Also mount any other modules to the plywood.
Figure 4-56 Components Layout for ECS-DUAL50W
4-43