High Velocity Cartridge Filters (Gk Series) - Greenheck 452413 Installation, Operation And Maintenance Manual

Canopy type kitchen hoods
Table of Contents

Advertisement

High Velocity Cartridge Filters
A. Exhaust
With all the filters in place, determine the total hood exhaust
volume with a rotating vane anemometer as follows:
1. All cooking equipment should be on. If the hood has
internal short circuit make-up air, it should be turned off.
2. Measuring Velocities
• Velocity measurement should be taken at three locations per filter.
These must be over the inlet opening as shown in Fig. 35.
• Measure the velocity of each location. A digital 2.75 in. (70 mm)
rotating vane anemometer or its equivalent is suggested. The center
of the anemometer should be held 2 in. (50 mm) from the face of
the filters as in Fig. 31. It is helpful to make brackets to keep the
anemometer at the 2 in. (50 mm) distance and parallel to the filter.
Both squareness and distance are important for accuracy.
3. Calculate the average slot velocity.
4. Calculate the CFM per linear foot by dividing the average velocity by a
conversion factor listed in the following table.
5. Calculate the hood's exhaust volume by multiplying the CFM per linear
foot by the length of hood.
Cartridge Filter Size
16 in. (400 mm) high with 4 in. (100 mm) high inlet
20 in. (500 mm) high with 4 in. (100 mm) high inlet
16 in. (400 mm) high with 7 in. (120 mm) high inlet
20 in. (500 mm) high with 7 in. (120 mm) high inlet
Example:
Measure the slot velocities in fpm for a 9 ft. (2.74 m) hood with four 20 x 20 in. (500 x 500 mm)
filters with standard opening, three readings per filter.
Average slot velocity
(Imperial)
(Metric)
CFM per linear foot
Hood exhaust volume
22
Canopy Hood
Sum of Velocity Readings
=
Number of Readings
5330
=
= 444.2 fpm
12
97474
=
= 8123 m/hr
12
Average Slot Velocity
=
Conversion Factor
444.2 fpm
=
= 206.6 cfm/linear foot
2.15
8123 m/hr
= 1152 m
=
7.05
=
CFM/linear foot (m
=
206.6
=
1152
1/4 Width
Imperial
Conversion Factor
3
ft
1.63 1/
3
ft
2.15 1/
3
ft
1.24 1/
3
ft
1.58 1/
3
/hr
3
/hr / m)
x
Hood Length
x
9 ft.
x
2.74 m
1/2 Width
1/4 Width
Fig. 35
2 in.
Rotation Vane
Anemometer
Fig. 36
Metric
Conversion Factor
3
m
5.35 1/
3
m
7.05 1/
3
m
4.07 1/
3
m
5.18 1/
Filter Readings (fpm)
470
440
425
482
430
453
455
431
441
399
439
465
Filter Readings (m/hr)
8595
8047
7772
8815
7864
8284
8321
7882
8065
7297
8028
8504
= 1859.4 cfm
=
3156 m
3
/hr
1/2
Inle
®