Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with these instructions will result in voiding of the product warranty and may result in personal injury
and/or property damage.
Vektor-MH, Vektor-MD, and Vektor-MS

Table of Contents

General Safety Information . . . . . . . . . . . . . . . . . . . . . .1
Unit and System Identification . . . . . . . . . . . . . . . . . .3
Pre-Installation Information / Electrical Disconnects
Moving Parts / Guards / Plenum Access Doors
Air Pressure and Suction . . . . . . . . . . . . . . . . . . . . . .3
System Components . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Roof Curb and Mounting Details . . . . . . . . . . . . . . . . .6
Rigging, Lifting and Installation . . . . . . . . . . . . . . . 7-8
Fans
Rigging, Lifting and Installation . . . . . . . . . . . . . . . . .8
Nozzle / Windband / Silencer / Stack Extension
Weatherhood Installation . . . . . . . . . . . . . . . . . . . . . .9
Plenum Drainage Piping / Trap Detail . . . . . . . . . . . . .10
Bypass Air Plenum - Isolation Damper Access and
Actuator Mounting . . . . . . . . . . . . . . . . . . . . . . . . . .11
Field Coating Touch-Up . . . . . . . . . . . . . . . . . . . . . . .11
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . .12
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Vibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
V-Belt Drive Installation . . . . . . . . . . . . . . . . . . . . . . . .16
Radial Gap and Alignment . . . . . . . . . . . . . . . . . . . . .16
Jib Crane Assembly (Optional) . . . . . . . . . . . . . . . . . .16
Bearing Replacement - Belt Drive . . . . . . . . . . . . . . .17
Vektor-MS Nozzle Parts and Assembly . . . . . . . . . . .18
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . Backcover
Our Commitment . . . . . . . . . . . . . . . . . . . . . . Backcover
®
Model Vektor
Laboratory Exhaust System

General Safety Information

Only qualified personnel should install this fan system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan rpm. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to a duct while the fan is
running.
DANGER
Always disconnect power before working on or near a
fan. Lock and tag the disconnect switch or breaker to
prevent accidental power up.
CAUTION
When servicing the fan, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
Document 464652
®
®
-MH, Vektor
-MD
®
and Vektor
-MS
Laboratory Exhaust Systems
1

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck Vektor-MH

  • Page 1: Table Of Contents

    Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage. Vektor-MH, Vektor-MD, and Vektor-MS General Safety Information Only qualified personnel should install this fan system.
  • Page 2: Receiving / Unpacking / Handling / Storage

    Fan wheels should be blocked to prevent spinning Extension, Discharge Nozzle, and Bypass Air Plenum. caused by strong winds. The Vektor-MH, Vektor-MD and Vektor-MS are designed Inspection and Maintenance during Storage to be self-supporting and standing (without the use of guy wires) when assembled per the instructions While in storage, inspect fans once per month.
  • Page 3: General Information

    Before opening access doors, ensure the fan wheel has Prior to fully assembling and installing the Vektor-MH, stopped moving and that the wheel has been secured Vektor-MD or Vektor-MS fans, inspect bypass air from being able to rotate.
  • Page 4: System Components

    System Components Vektor-MH Assembly View - Belt Drive Vektor-MD Assembly View - Direct Drive Belt and direct drive units share similar system Belt and direct drive units share similar system components and assembly configuration. components and assembly configuration. Windband High Plume Nozzle...
  • Page 5 Vektor-MS Assembly View - Direct Drive Belt and direct drive units share similar system components and assembly configuration. VGN Nozzle Blower Housing Bypass Air Plenum Roof Curb or Structural Support Blower Housing Access Door Isolation Damper Panel Isolation Damper Lifting Actuator Cover Points Weatherhood...
  • Page 6: Roof Curb And Mounting Details

    NOTE for additional details. Instructions are shipped with the Steel, concrete or wood roof support is per structural roof curb or can be found online at greenheck.com engineer and in accordance with load requirements under the library section. and applicable building codes.
  • Page 7: Bypass Air Plenum Rigging, Lifting And Installation

    Bypass Air Plenum - Rigging, Lifting and Installation Prior to lifting any components, verify the weights on Bypass Air Plenum Installation the project submittal drawings for each component Bypass air plenums (BAP) are delivered fully assembled or contact factory. Do not lift weights beyond the unless shipping restrictions require multiple sections.
  • Page 8: Rigging, Lifting And Installation

    Mounting the BAP to roof curbs from manufacturers fans are shipped with the nozzle separate from the main other than Greenheck Fan Corporation or not housing. For these sizes the nozzle should be lifted following proper mounting instructions may impact fan separate from the fan.
  • Page 9: Weatherhood Installation

    Nozzle and Windband Lifting and Installation Nozzle Lifting and Installation for Vektor-MH for Vektor-MD Using the nozzle lifting points, place nozzle over blower Lifting Lifting Point Point discharge, aligning support bracket Lifting holes with bolt holes in blower Point Windband housing.
  • Page 10: Duct Connections - Side Inlet / Bottom Inlet

    Duct Connections to the Bypass Air Plenum Drainage Piping / Trap Plenum (BAP) Detail (By Others) Connecting primary inlet exhaust air ducts is allowed through the roof curb or through one or more of the side access panels. To reduce the potential for system effects in the plenum, the duct connection should be sized to have no more than a maximum air velocity of 1500 fpm when entering.
  • Page 11: Actuator Mounting

    Bypass Air Plenum (BAP) and Field Coating Touch-Up for Isolation Damper Access and Scratched Areas Actuator Mounting Standard coating and color is LabCoat™ RAL 7023 Concrete Grey. Bypass Air Plenum Failure to perform touch-ups may result in rust or Depending on the configuration and intended operation corrosion and accelerate the fade in color and is not of the system supplied, the plenum section may not covered under warranty.
  • Page 12: Electrical Connections

    115/208/230/277 volt motor. Single phase Vektor-MH and Vektor-MD Motor Disconnect and Isolation Damper Wiring Diagram Three Phase Layout Disconnect is mounted to fan housing. Transformers are mounted to bypass air plenum with damper actuator...
  • Page 13: Start-Up

    Start-Up Additional steps for initial start-up WARNING 1. Check for proper wheel rotation by Disconnect and secure to the OFF position all momentarily energizing the fan. electrical power to the fan prior to inspection or Access to view the wheel can servicing.
  • Page 14: Vibration

    Vibration Routine Maintenance and Operation On start-up and during operation, the unit should operate smoothly with minimal vibration. It is possible CAUTION that a higher degree of vibration may be experienced. Excessive vibration if left unchecked, can cause a When performing any service to the fan, disconnect multitude of problems, including structural and/or the electrical supply and secure fan impeller.
  • Page 15 Do not install new belts on worn sheaves. If the sheaves Recommended Bearing Lubrication Schedule have grooves worn in them, they must be replaced Relubrication Schedule in Months* before new belts are installed. Synthetic Grease The proper tension for operating a V-belt drive is the Bearing Bore (inches) lowest tension at which the belts will not slip at peak ⁄...
  • Page 16: V-Belt Drive Installation

    Crane for Vektor. Instructions are shipped with the jib 2. Slide sheaves on shafts - do not drive crane or can be found online at greenheck.com under sheaves on as this may result in the library section.
  • Page 17: Bearing Replacement - Belt Drive

    Bearing Replacement The intent of this fan design with its large side access 8. Align the top of the bearing with the scribed mark openings is to allow a field service technician to replace indicating the correct mounting location. Secure bearings with the fan remaining in place in its intended lower bearing to bottom support plate.
  • Page 18: Vektor-Ms Nozzle Parts And Assembly

    Vektor-MS Nozzle Parts and Assembly Item Quantity Description Transition weld Transition side cover Wind wrap round Wind wrap flat Frame bottom bar Frame top bar Frame weld Blade weld 2 or 4* Actuator mount Lifting point 2 or 4* Actuator cover Blade seal, right Blade seal, left Flex backing...
  • Page 19: Troubleshooting

    Troubleshooting Problem Cause Corrective Action Adjust wheel and/or inlet cone. Wheel Rubbing Inlet Tighten wheel hub or bearing collars on shaft. Tighten sheaves on motor and fan shaft. Adjust belt tension. Align sheaves properly (see procedure). Excessive V-Belt Drive Replace worn belts or sheaves. Noise Replace defective bearing(s).
  • Page 20: Maintenance Log

    As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Product warranties can be found online at Greenheck.com, either on the specific product page or in the literature section of the website at Greenheck.com/Resources/Library/Literature.

This manual is also suitable for:

Vektor-mdVektor-ms