Burkert 8008 Instruction Manual

Burkert 8008 Instruction Manual

Flow / consumption sensor
Hide thumbs Also See for 8008:

Advertisement

Quick Links

EN - English
Instruction manual
Flow / consumption Sensor
Type 8008
Type 8008 English V1.17
Page 1 of 34

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 8008 and is the answer not in the manual?

Questions and answers

Summary of Contents for Burkert 8008

  • Page 1 EN - English Instruction manual Flow / consumption Sensor Type 8008 Type 8008 English V1.17 Page 1 of 34...
  • Page 2: Foreword

    Foreword Dear customer, thank you very much for deciding in favour of the Type 8008. Please read this installation and operation manual carefully before mounting and initiating the device and follow our advice. A riskless operation and a correct functioning of the...
  • Page 3: Table Of Contents

    4.1.2.2 Passive ........................9 4.1.3 Pulse ..........................9 4.1.4 Alarm ..........................9 Measuring range flow Type 8008 ..................10 Dimensions ........................11 Dimension Type 8008 Thread-version ................11 Dimension Type 8008 Flanged-version ................12 Installation ........................13 Pipe/tube requirements ....................... 13 Inlet / outlet runs ........................13 6.2.1...
  • Page 4 User Setup ........................30 8.3.4.1 Password ........................30 8.3.4.2 Language ........................30 8.3.4.3 Display / Touch ......................31 8.3.5 Advanced ......................... 31 8.3.6 4 -20mA ........................... 32 8.3.7 Type 8008 Info ......................... 34 Type 8008 English V1.17 Page 4 of 34...
  • Page 5: Pictograms And Symbols

    Note! Possible harzard As a consequence of incorrect handling: possible personal injury or damage Important! Additional notes, information, tips As a consequence of incorrect handling: Disadvantages in operation and maintenance, no danger Type 8008 English V1.17 Page 5 of 34...
  • Page 6: Safety Instructions

    Measures: • Make sure that the Type 8008 operates only within the permissible and listed limits on the nameplate • Ensure the operation within the performance data of Type 8008 in connection with the application •...
  • Page 7: Intended Use

    The instrument described in this manual is exclusively to use for measuring the thermal mass flow of gases. At the same time, the gas temperature is measured too. The Type 8008 can be configured for measuring a predetermined range of pure gases or of gas mixtures.
  • Page 8: Technical Data

    Screw in thread: Material: Housing aluminum die cast, probe stainless steel1,4571 Protection class IP67 * Reference conditions for Temperature and pressure can be freely set, standard conditions are 0 ° and 1013 mbar. Type 8008 English V1.17 Page 8 of 34...
  • Page 9: Signal Circuits

    Vin 12-36Vdc 4.1.3 Pulse  Galvanically isolated (dry contact)  Passive: 48Vdc , 500 mA  Max. pulse output freq. 50Hz 4.1.4 Alarm  Galvanically isolated (dry contact)  Max. 48Vdc, 500mA Type 8008 English V1.17 Page 9 of 34...
  • Page 10: Measuring Range Flow Type 8008

    Measuring Range Measuring range flow Type 8008 1/4" 1/2" 3/4" 1" 1 ¼" 1 ½" 2" 2 ½" 3" Analog Analog Analog Analog Analog Analog Analog Analog Analog output output output output output output output output output 20mA 20mA 20mA...
  • Page 11: Dimensions

    Dimension Dimensions Dimension Type 8008 Thread-version 138 (max) Ex version 156 (max) 132 (max) Flow direction Type 8008 thread version Connection Outer Inner thread pipe dia. pipe dia. [mm] [mm] [mm] [mm] [mm] [mm] [mm] 1/2“ 21,3 16,1 176,4 165,7 3/4“...
  • Page 12: Dimension Type 8008 Flanged-Version

    Dimension Dimension Type 8008 Flanged-version 138 (max) Ex version 156 (max) 132 (max) Flow direction VA 570 flanged version Flange DIN EN 1092-1 Outer Inner ØK Measuring pipe pipe ØD n x ØL dia. dia. [mm] [mm] [mm] [mm] [mm]...
  • Page 13: Installation

    The values represent the min.lenghts. In case the min. inlet / outlet runs could not be ensured, it must be expected to get increased or significant d eviations of the measurement values. Type 8008 English V1.17 Page 13 of 34...
  • Page 14: Installation Of Type 8008

    5.1 and chapter 5.2 Alignment Display (Housing) The sensor housing Type 8008 can be turned in both directions, max. 345 °. For this purpose, the housing-connecting nut must be opened. The housing can be rotated to the desired position, a bigger rotaion angle is prevented by internal stop pins.
  • Page 15: Connection Diagram

    Connection diagram Cable glands - clamping ranges For ensuring the tightness and strain relief, connector cables with the following diameters must be used. Type 8008 clamping range : Ø5-9mm Connector pin assignment Main Board Standard version with 1x analogue output (not galvanically...
  • Page 16: The Current Outputs, X5 And X6, Are Optional As Passive Output Available Too

    Pulse / Alarm * Direction input I- Active** I+ Active** I- Active** I+ Active** * Outputs are galvanically isolated. ** The Current outputs, X5 and X6, are optional as passive output available too. Type 8008 English V1.17 Page 16 of 34...
  • Page 17: Wire Cnnection

    Therfore the enclosed 120R resistor ist o be connected at Pin 1 and Pin 3 of connector „X2“ Main Board 120R 7.3.4 Pulse Output Main Board Potentialfreier Schaltkontakt Max. 48Vdc , 500mA Type 8008 English V1.17 Page 17 of 34...
  • Page 18: Operation Type 8008

    Operation Operation Type 8008 The operation of the Type 8008 are carried out by 2 optical keys through the glass cover Thus, the Type 8008 can be operated from the outside without opening the cap. Optical keys Selection of the individual menu items is done by pressing the ">" and confirm by pressing "OK".
  • Page 19: Main Menu (Home)

    Operation Main menu (Home) 8.1.1 Intialization After switching on the Type 8008 the initialized screen is displayed followed by the main menu. Flow Sensor Main menu *** VA 550 *** Gas type / Status Info HW Version Modbus ID Page-No.
  • Page 20: Settings

    Selection of a menu item or to change „ “, a a value is done with the key final move to the chosen menu item or takeover of the value change needs the „OK“ confirmation by pressing the key Type 8008 English V1.17 Page 20 of 34...
  • Page 21: Sensor Setup

    „ “ with key and then confirm it with “OK“. 8.3.1.1 Input / change tube diameter For Type 8008 not adjustable (suspended) as voted on included measuring section with corresponding pipe diameter. Type 8008 English V1.17 Page 21 of 34...
  • Page 22: Input / Change Consumption Counter

    In case the quantity of units selectable are not presentable on one page, pleas move to next „<<“ page by pressing Confirm selection by pressing 2x „OK“. Procedure for all 4 measurement-variables is analogous. Type 8008 English V1.17 Page 22 of 34...
  • Page 23: Definition Of The Reference Conditions

    Do not enter the operation pressure or the operation temperature under reference conditions Setup  Sensor Setup Advanced To make changes, first select a menu with „“ button and confirm selection by pressing „OK“ Type 8008 English V1.17 Page 23 of 34...
  • Page 24 Setup  Sensor Setup Advanced  AV-Time The time period for averaging can be entered here. Input values of -1440 1 [minutes] are possible. For average values see display window 3 + 4 Type 8008 English V1.17 Page 24 of 34...
  • Page 25: Setting Of Zeropoint And Low-Flow Cut Off

    Setup  Sensor Setup  ZP Adjust t  Reset „Reset“ By selection of all settings for 1,03 „ZeroPnt“ and. „CutOff“ are reset. „“ Menu item to be select with button „OK“ confirm the reset with „Back“ Leave menu with button Type 8008 English V1.17 Page 25 of 34...
  • Page 26: Modbus Setup

    Operation 8.3.2 Modbus Setup The Flow sensors Type 8008 comes with a Modbus RTU Interface. Before commissioning the sensor the communication parameters  Modbus ID, Baudrate, Parity und Stop bit must be set in order to ensure the communication with the Modbus master.
  • Page 27: Modbus Settings (2001

    Flow in cfm Flow in Ncfm 1189 1188 Float Flow in kg/h 1197 1196 Float 1205 1204 Float Flow in kg/min 1213 1212 Float Flow in kg/s Flow in kW 1221 1220 Float Type 8008 English V1.17 Page 27 of 34...
  • Page 28 UInt32 comma 1347 1346 Float Velocity m/s 1355 1354 Float Velocity Nm/s 1363 1362 Float Velocity Ft/min 1371 1370 Float Velocity NFt/min 1419 1418 Float GasTemp °C GasTemp °F 1427 1426 Float Type 8008 English V1.17 Page 28 of 34...
  • Page 29: Pulse /Alarm

    3000000 Table 1 Maximum flow for pulse output Entering pulse values that are not allow a presentation to the full scale value, are not allowed. Entries are discarded and error message displayed. Type 8008 English V1.17 Page 29 of 34...
  • Page 30: User Setup

    Language   Settings UserSetup Language Currently 4 languages have been implemented and could be selected with button „>“. Change of language by confirming with “OK”. “back”. Leaving the menu with button Type 8008 English V1.17 Page 30 of 34...
  • Page 31: Display / Touch

    10s. To do this, use the "OK" button to enter the operating menu during this period 8.3.5 Advanced Settings  Advanced „Factory Reset“ By pressing the sensor is set back to the factory settings. Type 8008 English V1.17 Page 31 of 34...
  • Page 32: -20Ma

    „OK“ and confirm selection by pressing  Settings  4-20mA Channel 1 The 4-20 mA Analogue output of the Sensor Type 8008 can be individually adjusted. It is possible to assign following values „Temperature“, „Velocity“ und „Flow“ to the channel CH 1.
  • Page 33 To make changes first select a menu item "Current Error" „“ „OK“ with button and then select by pressing the desired mode „Save“ For saving the changes done press button “Cancel”. discard the changes press button Leaving the menu with „Back“. Type 8008 English V1.17 Page 33 of 34...
  • Page 34: Type 8008 Info

    Operation 8.3.7 Type 8008 Info   Setup Sensor Setup Info Here you get a brief description of the sensor data incl. the calibration data. 92,7 m/s 600m³/h Under Details, you are able to see in addition the Run Time: 2d 21h 23m 12s calibration conditions.

Table of Contents