6 Troubleshooting

Indoor unit

6.2 Indoor unit

Alarms through PC-ARFTE
Outdoor
Alarm
Protection
unit LED301
code
code
Blinking
times
03
-
16
-
71
-
80
-
102
P102
2 times
103
P103
3 times
104
P104
4 times
105
P105
5 times
--
P106
6 times
107
P107
7 times
--
P109
9 times
--
P110
10 times
--
P111
11 times
112
P112
12 times
113
P113
13 times
114
P114
14 times
115
P115
15 times
--
P116
16 times
204
-
205
-
70
SMGB0135 rev.0 - 06/2020
Category
Type of abnormality
Transmission Alarm (Not 
Indoor
outdoor unit detected)
DHW tank thermistor 
Indoor
abnormally (THM
Tank over-temperature limit 
Indoor
protection
LCD controller transmission 
Indoor
error
Outdoor unit
LCD controller has no power
Abnormal Low Speed of the 
Outdoor unit
Compressor
Compressor Changeover 
Outdoor unit
Failure (Switching Failure)
Lower Limit of Compressor 
Outdoor unit
Overload
Stoppage by OH Thermistor 
Outdoor unit
High Temperature
Thermistor Failure: Thermistor 
Outdoor unit
disconnection short circuit
Stoppage by Transmission 
Outdoor unit
Error, communication error
Outdoor unit
Power Supply Voltage Error
Outdoor unit
Fan abnormality 1
Outdoor unit
Fan lock, Fan abnormality 2
Outdoor unit
EEPROM Error
Outdoor unit
Overvoltage abnormality
Outdoor unit
Circuit abnormality
Outdoor unit
Software Ip cut stop
Indoor unit stops answering to
LCD
PC-ARFTE
Central Alarm, no Central 
LCD
message 
Main cause
Loose, disconnected, broken or short-
circuited connector.
Loose, disconnected, broken or short-
)
circuited connector.
DHWT
Failure of control relay.
No H-link communication for a continuous 
period of 90 seconds between Indoor and 
LCD User control by connection wiring 
(breaking, wiring error, etc.).
Power supply problem or incorrect wiring.
Failure of compressor or PCB.
Pipe clogging, excessive refrigerant, innert 
gas mixing, fan motor locking at cooling 
operation.
Failure of compressor or PCB.
Failure of compressor or PCB.
Failure of compressor or PCB.
Incorrect wiring, disconnected wiring, 
broken cable, sensor failure.
Pipe clogging, excessive refrigerant, innert 
gas mixing, fan motor locking at cooling 
operation.
Incorrect wiring, disconnected wiring, 
broken cable, sensor failure.
Incorrect or disconnected wiring.
PCB failure.
Power supply problem or incorrect wiring.
Failure of compressor or PCB.
Failure of fan motor.
Failure of PCB.
Failure of fan motor.
Failure of PCB.
Failure of PCB.
Power supply problem or incorrect wiring.
Failure of compressor or PCB.
Failure of PCB.
Failure of compressor or PCB.
Loose, disconnected, broken or short-
circuited connector.
Loose, disconnected, broken or short-
circuited connector.