Carrier 50PEC09-18 Installation, Start-Up And Service Instructions Manual page 19

Water source heat pump console unit with puron refrigerant (r-410a) 50 hz
Table of Contents

Advertisement

AL
Alarm Relay Contacts
BM
Blower Motor
BR
Blower Relay
CAP
Capacitor
CB
Circuit Breaker
CO
Sensor, Condensate Overflow
CR
Compressor Relay
DM
Damper Motor
ES
End Switch
FP1
Sensor, Water Coil Freeze Protection
FP2
Sensor, Air Coil Freeze Protection
FSS
Fan Speed Switch
HP
High-Pressure Switch
HPS
High-Pressure Switch
HPWS
High-Pressure Water Switch
JW1
Jumper Wire for Alarm
LOC
Loss of Charge Pressure Switch
LON
Local Operating Network
PB
Power Terminal Block
RVS
Reversing Valve Solenoid
TRANS —
Transformer
WV
Water Valve
LEGEND
----------
Fig. 18 — 50PEC Unit with Complete C and LON Controllers
Complete C
Field Line Voltage Wiring
Field Low-Voltage Wiring
Option Low-Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
19
Complete C
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally pro-
tected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 240-V (ORG) lead for
240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or may
have a circuit breaker.
4. FP1 thermistor provides freeze protection for
water. When using anti-freeze solutions, cut JW3
jumper.
5. Low voltage wiring must be class 1 and voltage
rated equal or greater than unit supply voltage.
6. Factory cut jumper (JW1). Dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via GRN/YEL
wire from C to control box.
8. See view A for wiring of units with water valve
(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).