Carrier 50PEC09-18 Installation, Start-Up And Service Instructions Manual
Carrier 50PEC09-18 Installation, Start-Up And Service Instructions Manual

Carrier 50PEC09-18 Installation, Start-Up And Service Instructions Manual

Water source heat pump console unit with puron refrigerant (r-410a) 50 hz

Advertisement

Installation, Start-Up and Service Instructions
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
Step 1 - Check Jobsite . . . . . . . . . . . . . . . . . . . . . . . . 2
Step 2 - Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• UNIT PROTECTION
Step 3 - Mount Unit . . . . . . . . . . . . . . . . . . . . . . . . . . 17
• EXTERNAL LOOP POWER CONNECTION
• SUPPLY AND RETURN HOSES
• SUPPLY AND RETURN PIPING
Step 7 - Install Condensate Piping . . . . . . . . . . . . 26
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-29
System Cleaning and Flushing . . . . . . . . . . . . . . . . 27
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
FIELD SELECTABLE INPUTS . . . . . . . . . . . . . . . .29,30
Complete C Control Jumper Settings. . . . . . . . . . . 29
Complete C Control DIP Switches. . . . . . . . . . . . . . 29
Deluxe D Control Jumper Settings . . . . . . . . . . . . . 29
Deluxe D Control DIP Switches . . . . . . . . . . . . . . . . 29
Deluxe D Control Accessory
Relay Configurations . . . . . . . . . . . . . . . . . . . . . . . 30
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-32
Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Unit Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Flow Regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . 32
Heat Exchanger Well Systems . . . . . . . . . . . . . . . 32
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32,33
Power Up Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
SYSTEM TEST. . . . . . . . . . . . . . . . . . . . . . . . . . . .33,34
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-36
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
System Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Water Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500075-01
Water Source Heat Pump Console Unit with
Page
Printed in U.S.A.
Form 50PEC-C1SI
PURON
®
Refrigerant (R-410A)
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Condensate Pans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Blower Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Safety Control Reset. . . . . . . . . . . . . . . . . . . . . . . . . . 35
Checking System Charge . . . . . . . . . . . . . . . . . . . . . 36
Refrigerant Charging . . . . . . . . . . . . . . . . . . . . . . . . . 36
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . 36
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . .36-38
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Control Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
START-UP CHECKLIST. . . . . . . . . . . . . . . . . CL-1, CL-2
IMPORTANT: Read the entire instruction manual before
starting installation.

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can
be hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install,
repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All other
operations should be performed by trained service personnel.
When working on air-conditioning equipment, observe precau-
tions in the literature, tags and labels attached to the unit, and
other safety precautions that may apply.
Improper installation, adjustment, alteration, service, mainte-
nance, or use can cause explosion, fire, electrical shock or other
conditions which may cause personal injury or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory-authorized kits or accesso-
ries when modifying this product. Refer to the individual
instructions packaged with the kits or accessories when
installing.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have fire
extinguisher available. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult
local building codes and applicable electrical codes for special
installation requirements.
Understand the signal words - DANGER, WARNING, and
CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death. WARNING
signifies hazards that could result in personal injury or death.
CAUTION is used to identify unsafe practices, which would re-
sult in minor personal injury or product and property damage.
Pg 1
AQUAZONE™
50PEC09-18
50 Hz
Page
9-10
Replaces: New

Advertisement

Table of Contents
loading

Summary of Contents for Carrier 50PEC09-18

  • Page 1: Table Of Contents

    Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500075-01 Printed in U.S.A. Water Source Heat Pump Console Unit with PURON ® Refrigerant System ......34 Page Condenser Cleaning .
  • Page 2: General

    There may be more than one disconnect switch. Turn off accessory heater power if applicable. GENERAL The 50PEC water source heat pump console unit is a decen- tralized room terminal designed for field connection to a closed-circuit piping loop.
  • Page 3 1.62 (41) 2.00 (51) CONTROL BOX COMPRESSOR ACCESS WATER IN PANEL 8.00 MIN (203) a50-8335 oNAL IZED aLVE 2.25 (57) oNNECTIONS CONDENSATE 5/8" (15.9) ID VINYL HOSE LEGEND EPT — External Pipe Thread IPT — Internal Pipe Thread *Dimension reduced by fitting if selected. NOTE: Dimensions shown are in inches.
  • Page 4 1.75 (44) CONTROL BOX COMPRESSOR ACCESS PANEL WATER CONNECTIONS 7/8” (22.2) OD COPPER, 3/4” IPT OR 3/4” EPT 2.12 (54) CONDENSATE 5/8" (15.9) ID VINYL HOSE LEGEND EPT — External Pipe Thread IPT — Internal Pipe Thread *Dimension reduced by fitting if selected. NOTE: Dimensions shown are in inches.
  • Page 5 Filter located inside and at top of air inlet area. Rotate filter latch forward, filter rack can be pulled forward 75 to 100 mm for filter access AIR INLET AREA 33.5 1.75 (851) (44.5) 1.0 (25) (114) 1.0 (25) R.H. REAR 20.0 ACCESS...
  • Page 6 Filter located inside and at top of air inlet area. Rotate filter latch forward, filter rack can be pulled forward 75 to 100 mm for filter access AIR INLET AREA 39.50 1.75 (1003) (44.5) 4.50 1.00 (25) (114) 1.00 (25) RH REAR 20.00 ACCESS...
  • Page 7 Filter located inside and at top of air inlet area. Rotate filter latch forward, filter rack can be pulled forward 75 to 100 mm for filter access AIR INLET AREA 33.5 1.75 (851) (44.5) L.H. PIPE AND ELECTRIC AREA 10.0 6.88 (254) NOTE 2...
  • Page 8 Filter located inside and at top of air inlet area. Rotate filter latch forward, filter rack can be pulled forward 75 to 100 mm for filter access AIR INLET AREA 39.50 1.75 (1003) (44.5) L.H. PIPE AND ELECTRIC AREA 6.88 10.00 (Note 2) (254)
  • Page 9 21.0 (533) 12.0 BOTTOM VIEW (305) 1.0 (25) (114) 1.0 (25) 20.0 (508) R.H. REAR ACCESS (NOTE 2) NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3.
  • Page 10 21.00 (533) 12.00 BOTTOM VIEW (305) 4.12 (105) 1.00 (25) 1.00(25) 20.00 (508) RH REAR ACCESS (NOTE 2) NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3.
  • Page 11 (89) ° .50 (13) 11.50 (Note 2) (292) (19) 4.12 (105) L.H. (NOTE 2) a50-8345 NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3. Optional autoflow valve, motorized water valve and disconnect box are shown. Fig.
  • Page 12 21.00 (533) (13) L.H. PIPE AND 11.50 ELECTRIC AREA (292) (Note 2) (19) 4.12 (105) REAR VIEW NOTES: 1. Dimensions are shown in inches. Dimensions in parentheses are in millimeters. 2. Access is reduced if optional disconnect box is selected. 3.
  • Page 13 a50-8347...
  • Page 14 a50-8348...
  • Page 17: Step 2 - Check Unit

    Table 2. SHIPPING BOLTS Fig. 15 — Remove 4 Shipping Bolts on Compressor Isolator Plate HEAT PUMP WARNING Disconnect electrical power source to prevent injury or death from elec- trical shock. CAUTION Use copper conductors only to prevent equipment damage.
  • Page 18 Complete C — Alarm Relay Contacts — Blower Motor — Blower Relay — Capacitor — Circuit Breaker — Sensor, Condensate Overflow — Compressor Relay — Damper Motor — End Switch — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection —...
  • Page 19 — Alarm Relay Contacts — Blower Motor — Blower Relay — Capacitor — Circuit Breaker — Sensor, Condensate Overflow — Compressor Relay — Damper Motor — End Switch — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection —...
  • Page 20 Deluxe D LEGEND — Alarm Relay Contacts — Blower Motor — Capacitor — Circuit Breaker — Sensor, Condensate Overflow — Compressor Relay — Damper Motor — End Switch — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection —...
  • Page 21 Deluxe D LEGEND — Alarm Relay Contacts — Blower Motor — Blower Relay — Capacitor — Circuit Breaker — Sensor, Condensate Overflow — Compressor Relay — Damper Motor — End Switch — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection —...
  • Page 22 Complete C — Alarm Relay Contacts — Blower Motor — Blower Relay — Capacitor — Circuit Breaker — Sensor, Condensate Overflow — Compressor Relay — Damper Motor — End Switch — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection —...
  • Page 23 Deluxe D LEGEND — Alarm Relay Contacts — Blower Relay — Capacitor — Circuit Breaker — Sensor, Condensate Overflow — Compressor Relay — Damper Motor — Sensor, Water Coil Freeze Protection — Sensor, Air Coil Freeze Protection — Fan Speed Switch —...
  • Page 24 LEGEND — Control Relay LWT — Leaving Water Temperature Sensor SAT — Supply Air Temperature Sensor SPT — Space Temperature Sensor NOTE: Reversing valve is on in Cooling mode. Fig. 23 — PremierLink™ Controller Applications with Complete C Control LEGEND LWT —...
  • Page 25: Supply Voltage

    50PEC VOLTAGE V-Ph-Hz UNIT SIZE CODE 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Locked Rotor Amps — Rated Load Amps Make all final electrical connections with a length of flexi- ble conduit to minimize vibration and sound transmission to the building.
  • Page 26: Optional Wall-Mounted Thermostat

    Fig. 17-20. When desired, the unit can be furnished with a 24-v control circuit which is field wired to a Carrier-supplied accessory re- mote thermostat. Most heat pump thermostats can be used with the controller. Use a thermostat with Y, G, O and W outputs.
  • Page 27: Pre-Start-Up

    PRE-START-UP System Cleaning and Flushing — flushing the unit and system is the single most important step to ensure proper start-up and continued efficient operation of the system. WARNING To prevent injury or death due to electrical shock or contact with moving parts, open unit disconnect before servicing unit.
  • Page 28 Check equipment for proper temperature set 37.8 29.4 points and operation. 10.0 10.0 5. Balanced Water Flow Rate to Heat Pump: Record the 21.1 inlet and outlet water temperatures as each heat pump 26.7 unit is started. This check will eliminate nuisance unit –1.1 –6.7...
  • Page 29: Field Selectable Inputs

    Cooling Stage 2, W1 is used for Heating Stage 1 and O/W2 is used for Heating Stage 2. Select ON for heat pump applica- tions. In heat pump mode, Y1 used is for Compressor Stage 1, Y2 is used for Compressor Stage 2, W1 is used for Heating Stage 3 or emergency heat, and O/W2 is used for RV (heating or cooling) depending upon switch 4 setting.
  • Page 30: Relay Configurations

    1. Adjust all valves to the full open position and turn on the line power to all heat pump units. 2. Operate each unit in the Cooling mode first. Room temperature should be in the normal range (i.e., approximately 10.0 to 26.7 C dry bulb).
  • Page 31: Unit Start-Up

    16 C and 35 C. 5. Two factors determine the operating limits of Carrier heat pumps, return air temperature and water temperature. When any one of these factors is at a minimum or maxi- mum level, the other factor must be at normal level to en- sure proper unit operation.
  • Page 32: Cooling Tower/Boiler Systems

    Cooling Tower/Boiler Systems — typically use a common loop maintained at 15.6 C to 32.2 C. Carrier recommends using a closed circuit evaporative cooling tower with a secondary heat exchanger between the tower and the water loop. If an open type cooling tower is used continu- ously, chemical treatment and filtering will be necessary.
  • Page 33: Complete C And Deluxe D Board System Test

    immediately when the Cooling Stage 1 demand is removed. The control reverts to Standby mode. The RV relay remains on until there is a heating demand. If there is a master/slave or dual compressor application, all compressor relays and related functions will track with their associated DIP switch 2 on S1.
  • Page 34: Service

    Table 14 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations STATUS LED DESCRIPTION (Green) Normal Mode Normal Mode with PM D Control is non-functional Test Mode — Night Setback Flashing Code 2 Flashing Code 3 Invalid T-stat Inputs Flashing Code 4 No Fault in Memory HP Fault...
  • Page 35: Condensate Pans

    Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment anal- ysis is recommended. Refer to the Carrier System Design Man- ual, Part 5, for general water conditioning information. CAUTION Follow all safety codes.
  • Page 36: Checking System Charge

    WARNING When replacing the compressor contactor or lockout relay in a unit with electromechanical controls, use only Carrier factory authorized parts. Substitution of other components may result in an inoperative safety circuit and may cause a hazardous condition. Units are shipped with Checking System Charge —...
  • Page 37 Ensure thermostat set for heating or cooling operation. Unit locked out Check for lockout codes. Reset power. Compressor overload Check compressor overload. Replace if necessary. Thermostat wiring Check Y and W wiring at heat pump. Jumper Y and R for compressor operation in Test mode. SOLUTION...
  • Page 38 POSSIBLE CAUSE Thermostat wiring Check G wiring at heat pump. Jumper G and R for fan operation. Check Y and W wiring at heat pump. Jumper Y and R for compressor operation in Test mode. Fan motor relay Jumper G and R for fan operation. Check for line voltage across BR contacts.
  • Page 39: Start-Up Checklist

    CUSTOMER:___________________________ MODEL NO.:___________________________ I. PRE-START-UP DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N) HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS TIGHT? (Y/N) HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER? (Y/N) HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N) HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)
  • Page 40 SUBCOOLING = SATURATED CONDENSING TEMPERATURE – LIQUID LINE TEMPERATURE (DEG C) *Use 500 for water, 485 for antifreeze. Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500075-01 Printed in U.S.A.

Table of Contents