Major Disassembly; Front Engine Access - Generac Power Systems 10 kW LP Repair Manual

Automatic standby generators
Hide thumbs Also See for 10 kW LP:
Table of Contents

Advertisement

sEctioN 6.1

maJor DisassEmBlY

Front enGine acceSS

SAFETY:
1. Set the AUTO-OFF-MANUAL switch to OFF.
2. Remove the 7.5 amp main fuse. See Figure 1.
3. Remove the N1 and N2 fuse from the transfer switch.
Figure 1. Remove 7.5 Amp Fuse
4. Turn off fuel supply to the generator and remove the flex-
line from the fuel regulator.
5. Remove utility power from the generator.
6. Remove front door.
7. Remove battery from the generator.

FRONT ENGINE ACCESS:

1. Remove Controls Cover: Using a Torx T-27 socket
remove two bolts and ground washer from the controls
cover. Remove the controls cover. See Figure 2.
Figure 2.
Page 152
Part 6
2. Remove controller: Using a Phillips screwdriver remove the
four mounting screws from the controller. See Figure 3.
Figure 3.
3. Remove control harnesses:
a. Remove engine wiring harness at the J1 port.
b. Remove control wiring harness at the J2 port.
c. Remove stepper motor wiring harness at the J3
Figure
port. See
4.
Figure 4.
DISASSEMBLY

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents