Temperature Setting; Monitor Lights - Electro Industries EM-WX01-120-1-06 Quick Start Manual

Boost heater
Table of Contents

Advertisement

Temperature Setting

The inside circuit board contains two screwdriver switches marked Ø through 7. Adjust them to select the
desired set point for your application.
EX: Ideal set point = 86°
Mode Dial would be set to #4
Warm Air Dial would be set to #0
NOTE: MODE DIAL setting # 7 is not applicable to this product
Mode Dial Temperature Range Options
WARM AIR DIAL 
‐10 
‐7 
‐4 
‐1 
11 

Monitor Lights

The green LED on the circuit board indicates power at the electric element or modulation of the electric
element. For example, when the LED is on, full power is at the electric element.
Sequence
A. Electric element is on for 10 seconds after the application of 24 volts AC between yellow and black
wire.
B. Electric element turns off if the temperature is above the warm air set point.
C. If the temperature drops below warm air set point, the electric element modulates to bring it back to
the desired temperature level.
D. If the electric element is fully on (LED on constant) this unit cannot make up the air temperature
required between the duct inlet air and the temperature set point at the sensor probe.
04/27/2021
MODE DIAL 
14 
38 
62 
17 
41 
65 
20 
44 
68 
23 
47 
71 
26 
50 
74 
29 
53 
77 
32 
56 
80 
35 
59 
83 
3
86 
110 
134 
89 
113 
137 
92 
116 
140 
95 
119 
140 
98 
122 
140 
101 
125 
140 
104 
128 
140 
107 
131 
140 
MUA II 
EI912