W
ARM
COMFORT MODULE
Specific Application
 Air exchanger, temperature boost
 Make-up air
 Temperature comfort boost
 Air source HP comfort boost
Comment
This module is a heating element and controller to "temper" the supply air and bring it to a
comfortable level. For general duct temperature boost or heat pump comfort, this unit raises
the warm air supply temperature to the set point temperature value desired. In the make-up
air application the supply or inlet is actually outside air. This unit contains a built-in
controller with duct sensor to modulate the electric element (part of this unit) using only the
required electric energy to reach comfort level. This is more than basic on/off.
This is a single (duct temperature) WarmFlo sensor product. If you need the outdoor sensor
WarmFlo controller, call factory for other models.
MODELS
EM-WC0515H
EM-WC0515L
EM-WC1025H
EM-WC1025L
Drawings:
EL907, HH313, HH315, HH321, UAW878, UAW880, XX017
04/27/2021
4,800 WATT AT 240 VOLT, SINGLE PHASE
4,800 WATT AT 240 VOLT, SINGLE PHASE
9,600 WATT AT 240 VOLT, SINGLE PHASE
9,600 WATT AT 240 VOLT, SINGLE PHASE
F
LO
®
HI326

Advertisement

Table of Contents
loading

Summary of Contents for Electro Industries WarmFlo EM-WC0515H

  • Page 1 ® COMFORT MODULE Specific Application  Air exchanger, temperature boost  Make-up air  Temperature comfort boost  Air source HP comfort boost Comment This module is a heating element and controller to “temper” the supply air and bring it to a comfortable level.
  • Page 2: Electrical Requirements

    GENERAL This is a completely functional electric heat element package with the built-in WarmFlo, duct sensing, controller. It is installed in the main distribution duct or external to the heat pump unit/air handler. This module can be installed upflow, downflow, or horizontal. However, it must always be on the warm air side of the HP coil.
  • Page 3: Installation Requirements

    1. All installation work must be performed by trained, qualified contractors or technicians. Electro Industries, Inc., sponsors installation and service schools to assist the installer. 2. All electrical wiring must be in accordance with national electric codes and local electric codes, ordinances, and regulations.
  • Page 4 CLEARANCE – DUCT SURFACE AREAS, DUCT INSTALLATION, ETC. When installed within air handler plenum or furnace/A-coil plenum, the codes and rules relating to clearance apply. When installed in an “inline” duct or round pipe adapter for a general distribution boost heater or air make-up application, observe the following guidelines: 1.
  • Page 5: Installation

    TEMPERATURE RISE COMMENTS Typically the maximum temperature rise for this product is 40°F for room air inlet or 20°F for elevated supply temperature from a typical heat pump. If it is air make-up, outside air, larger temperature rises are permissible, see table above. INSTALLATION Locate the appropriate location where this element will temper all the air going to the room registers or distribution ducting.
  • Page 6: Electrical Hook-Up

    ELECTRICAL HOOKUP 240-volt source – from the model number and nameplate determine KW size and amp draw. According to local codes, building type, wiring length, etc. use appropriate wiring conductor size and source circuit breaker. Connect to the pigtail wires or terminal block. Grounding –...
  • Page 7: Operational Tips

    OPERATIONAL TIPS Comfort Level Temperature Setting The inside circuit board contains two screwdriver switches marked 0 through 7. Adjust them to select the desired set point for your application. EX: Ideal set point = 86° Mode Dial would be set to #4 Warm Air Dial would be set to #0 NOTE: MODE DIAL setting # 7 is not applicable to this product Mode Dial Temperature Range Options...
  • Page 8: Monitor Lights

    MONITOR LIGHTS The green LED on the circuit board indicates power at the electric element or modulation of the electric element. In other words, when the LED is on, full power is at the electric element. Sequence A. Electric element is on for 10 seconds after the application of 24 volts AC between yellow and black wire.
  • Page 9 Specification Sheet - Electric Make-Up Air/Boost Heater STANDARD EQUIPMENT 240V, single phase, external fusing required ▪ Temperature sensing with full modulation ▪ Quiet DC power relays ▪ Maintains specific temperature set point ▪ Thermostat end switch connection point ▪ Unique design allows for simplified installation ▪ Hi-limits, automatic reset - 150° F/180° fused link ▪...
  • Page 10 10.94" 15.64" 4.91" 5.75" 7.88" ELECTRO INDUSTRIES, INC. MONTICELLO, MN 55362 ART-278-00 2.0 Installation Specifications When installing this duct heater, NEC 424, Part IV, Duct Heaters, applies. When installed in an “inline” duct or round pipe adapter for a general distribution boost heater or make-up air application, observe the following guidelines: 1.
  • Page 17 Limited Product Warranty Effective November 1, 2009 Electro Industries, Inc. warrants to the original owner, at the original installation site, for a period of two (2) years from date of original purchase, that the product and product parts manufactured by Electro Industries, Inc.
  • Page 18: Conditions And Limitations

    The decision whether to repair or, in the alternative, replace products or product parts shall be made by Electro Industries, Inc. or its authorized representative.