System Service Checks; Maintenance - Lennox ALLIED Commercial TCA180S2B Standard Manual

Table of Contents

Advertisement

TABLE 12
TCA210H NORMAL OPERATING PRESSURES
CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4
Outdoor
Coil
Dis.
Suc.
Dis.
Entering
+10
+5
+10
Air Temp
psig
psig
psig
65°F
170
77
173
75°F
197
78
198
223
79
225
85°F
255
81
255
95°F
289
83
287
105°F
115°F
329
85
323
TABLE 13
TCA240S NORMAL OPERATING PRESSURES
CIRCUIT 1
Outdoor
Coil
Dis.
Suc.
Entering
+10
+5
Air Temp
psig
psig
185
69
65°F
212
71
75°F
236
72
85°F
267
73
95°F
105°F
297
74
115°F
335
76
TABLE 14
TCA240H NORMAL OPERATING PRESSURES
CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4
Outdoor
Coil
Dis.
Suc.
Dis.
Entering
+10
+5
+10
Air Temp
psig
psig
psig
65°F
179
75
181
75°F
207
76
208
239
78
238
85°F
272
80
270
95°F
307
83
303
105°F
115°F
351
85
342
TABLE 15
TCA300S NORMAL OPERATING PRESSURES
CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4
Outdoor
Coil
Dis.
Suc.
Dis.
Entering
+10
+5
+10
Air Temp
psig
psig
psig
185
69
183
65°F
213
72
210
75°F
247
75
241
85°F
280
77
271
95°F
105°F
320
79
309
115°F
361
81
346
Suc.
Dis.
Suc
Dis.
Suc.
+5
+10
+5
+10
+5
psig
psig
psig
psig
psig
80
172
80
168
80
81
197
81
193
81
82
225
82
221
82
83
257
83
252
83
84
293
85
287
85
86
333
87
327
87
CIRCUIT 2
CIRCUIT 3
Dis.
Suc.
Dis.
Suc.
+10
+5
+10
+5
psig
psig
psig
psig
182
73
183
72
209
75
210
74
233
75
234
75
265
76
264
75
301
77
300
76
340
78
338
78
Suc.
Dis.
Suc
Dis.
Suc.
+5
+10
+5
+10
+5
psig
psig
psig
psig
psig
79
174
79
176
79
81
203
79
204
80
82
233
80
234
81
83
266
83
266
83
84
301
84
300
85
85
343
86
342
86
Suc.
Dis.
Suc
Dis.
Suc.
+5
+10
+5
+10
+5
psig
psig
psig
psig
psig
70
186
72
179
71
74
215
76
207
75
77
249
78
240
78
78
281
80
271
79
79
317
81
307
80
80
358
82
345
82
Charge Verification − Approach Method
1− Using the same thermometer, compare liquid temper-
ature to outdoor ambient temperature.
Approach Temperature = Liquid temperature minus
ambient temperature.
2− Approach temperatures should match values in table
16. An approach temperature greater than
dicates an undercharge. An approach temperature
less than
this value
3− Do not use the approach method if system pressures
do not match pressures in tables 9 through 15. The ap-
proach method is not valid for grossly over or under-
charged systems.
APPROACH TEMPERATURES
Liquid Temp. Minus Ambient Temp.
Unit
1st Stage
180S
210S
7°F + 1
240S
(3.9°C + 0.5)
180H
9°F + 1
210H
(5°C + 0.5)
10°F + 1
240H
(5.6°C + 0.5)
14°F + 1
300S
(7.8°C + 0.5)
V− SYSTEMS SERVICE CHECKS
A−Cooling System Service Checks
TCA units are factory charged and require no further adjust-
ment; however, charge should be checked periodically using
the approach method. The approach method compares actual
liquid temperature with the outdoor ambient temperature. See
section IV−CHARGING.
NOTE−When unit is properly charged discharge line pres-
sures should approximate those in tables 9 through 15.
VI−MAINTENANCE
Electrical shock hazard. Turn off power to unit be-
fore performing any maintenance, cleaning or
service operation on the unit.
CAUTION
Danger of sharp metallic edges. Can cause injury.
Take care when servicing unit to avoid accidental
contact with sharp edges.
Page 35
this value
indicates an overcharge.
TABLE 16
2nd Stage
3rd Stage
7°F + 1
7°F + 1
(3.9°C + 0.5)
(3.9°C + 0.5)
7°F + 1
8°F + 1
(3.9°C + 0.5)
(4.4°C + 0.5)
(4.4°C + 0.5)
9°F + 1
9°F + 1
(5°C + 0.5)
(5°C + 0.5)
(5.6°C + 0.5)
12°F + 1
12°F + 1
(6.7°C + 0.5)
(6.7°C + 0.5)
(6.7°C + 0.5)
CAUTION
in-
4th Stage
NA
8°F + 1
10°F + 1
12°F + 1

Hide quick links: