Mitsubishi Electric Ecodan HUS210FTC4ST Installation Manual page 40

Pre-plumbed cylinder with ftc4 control system
Table of Contents

Advertisement

Electrical Installation
24
A.
Earth terminal
B.
Terminal block
C.
Clamp
D.
Service panel
E.
Wire the cables so
that they do not contact
the centre of the service
panel
Outdoor Model Number
Outdoor unit power supply
Outdoor unit Circuit Breaker Capacity
Wiring Wire
No. x size
(mm²)
Circuit
Rating
*1.
A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker
(NV). The breaker shall be provided to ensure disconnection of all active phase conductors of the supply.
*2.
Max. 120 m
*3.
The values given in the table above are not always measured against the ground value.
FTC4 Installation Manual
40
*
1
Outdoor unit power supply
including earth
Interface unit/flow temp.
*
2
controller– outdoor unit
Remote controller-Interface
unit/ Flow temp. controller
Outdoor unit L-N (single)
*
3
Outdoor unit L1-N, L2-N,
L3-N (3 phase)
Interface unit/Flow temp.
*
3
controller-outdoor unit
S2-S3
Remote controller-Interface *
3
unit/Flow temp.
controller
(continued)
PUHZ-
PUHZ-
W50VHA-BS
W85VHA(2)-BS
~/N (single),
~/N (single),
50Hz, 230V
50Hz, 230V
16 A
32 A
3 x Min. 2.5
3 x Min. 4
2 x 1.5
2 x 1.5
(polar)
(polar)
2 x 0.3
2 x 0.3
(non-polar)
(non-polar)
AC 230 V
AC 230 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V
PUHZ-
PUHZ-
HW140VHA(2)-BS
HW140YHA(2)-BS
~/N (single),
3N (3 phase),
50Hz, 230V
50Hz, 415V
40 A
16 A
3 x Min. 6
5 x Min. 2.5
2 x 1.5
3 x 1.5
(polar)
(polar)
2 x 0.3
2 x 0.3
(non-polar)
(non-polar)
AC 230 V
AC 415 V
DC 24 V
DC 24 V
DC 12 V
DC 12 V