FORM NO.: 6U6K-B01E-NB-EN
pressures detected are measured by gauge pressure. The ratio
must be kept in a certain range to make sure the compressor is
running within its envelope.
Compress ratio = (Pd+100) / (Ps+100);
Where:
Pd: Discharge gauge pressure, kPa;
Ps: Suction gauge pressure, kPa.
The ratio limitations are listed in Table 35 when loading is
prevented.
TABLE 35 - COMPRESS RATIO LOADING PREVENT-
ION LIMITATIONS
Fixed Speed SYS.
Inverter SYS.
TABLE 37 - COOLING DT LIMITATIONS
DT (°C)
DT<108°C
108≤DT≤111
111<DT≤115
DT>115
DT>115

INVERTER FREQUENCY CONTROL

The frequency of the inverter compressor start-up, operation
and stop when rising speed and descending speed should be in
accordance with the figure below.
The compressor must be maintained on the stable platform (40
to 75 RPS, 50 as default) for at least 1 minute before load or
unload.
The frequency change rate of rising speed and descending
speed is 1 RPS (revolution per second).
JOHNSON CONTROLS
Cooke Industries - Phone: +64 9 579 2185
Cooling
Heating
6.2
6.6
7.8
7.8
Duration (s)
/
Normal operation
/
Load prevented
/
Unload 1Hz/5s
<30
Unload 2Hz/5s
Reduce to minimum frequency (40Hz)
≥30
Email: sales@cookeindustries.co.nz
SECTION 9 – UNIT OPERATION
The ratio limitations are listed in Table 36 when unload is
mandatory.
TABLE 36 - COMPRESS RATIO UNLOAD LIMITATIONS
Fixed Speed SYS.
Inverter SYS.

DISCHARGE TEMPERATURE CONTROLS

Discharge temperature controls are available on inverter
system. External temperature sensors are fitted in the discharge
lines of each compressor for continuous detection. The inverter
compressor will be prevented to load or forced to unload if the
temperature is too high. The limitations in cooling mode are
listed in Table 37.
Inverter Compressor
RPS
(40-75)
RPS
1RPS
5
1 minute or more
FIGURE 42 – INVERTER LOADING PROCESS
Web: www.cookeindustries.co.nz
Cooling
Heating
8.1
8.1
8.1
8.1
Target
1RPS
1RPS
Target
Time