Operating Instructions
Data Logger PreLOG (15190)
9.5.2
Utilities – PreLOG Reboot
The function "PreLOG Reboot" can be used to reboot the PreLOG. In the process the RAM will be deleted, the
confi guration loaded from the fl ash memory, the fl ash memory initialised again and a connected modem reset. A
successful reboot will be reported in a message box.
Tip: At a reboot of the PreLOG neither recorded data as nor the values "Precipitation Amount
Between Retrievals" and "Precipitation Amount since Switch On" will not be deleted.
9.5.3
Utilities – PreLOG Clear Flash Memory
The function "PreLOG Clear Flash Memory" completely clears the fl ash memory of the PreLOG. This may be
useful after a maintenance, if artifi cially generated data from a simulation were written on the PreLOG memory. A
successful deletion will be reported in a message box.
Attention: The function "Clear Flash Memory" deletes all data in the fl ash memory. Please retrieve
all data from the PreLOG before using this function.
9.5.4
Utilities – PreLOG Reset Total Precipitation Amount
With the function "PreLOG Reset Total Precipitation Amount" you can reset the value for the precipitation amount
since switch on of the PreLOG to zero. A successful reset will be reported by a message box.
9.5.5
Utilities – PreLOG Critical Error
At switch on or reboot the PreLOG does a self-checking of its hardware. If any errors are detected, the PreLOG
will not start to record data and reports a critical error. The description of these critical errors can be displayed
with the function "PreLOG Critical Error".
If a critical error occurs, please check the PreLOG immediately and contact the LAMBRECHT service department
(+49-5514958390), since the PreLOG cannot proceed as long as a critical error exists.
9.5.6
Utilities – PreLOG Firmware Update
The function "PreLOG Firmware Update" can be used to load a new fi rmware into the EEPROM memory of the
PreLOG. This might be necessary if new program features or improvements are available.
Attention! In the fi rmware updating process all data in the fl ash memory will be deleted. Therefore
please retrieve all data from the fl ash memory before updating the fi rmware.
To perform a fi rmware update please follow these steps:
1.
Select the interface the PreLOG is connected to.
2.
Select the installation fi le of the new fi rmware and start the fi rmware update.
3.
After a successful update please check the confi guration and time of the PreLOG. Correct the settings if
necessary.
10

Inspection and Troubleshooting

It is recommended to perform visual and functional inspections on a regular basis at least once a year. The PreLOG
is highly insensitive to external contamination. Nevertheless it should be ensured that no contaminations enter into
the interfaces or that they are not accessible due to severe icing. The inspection intervals have to be adjusted to
the respective environmental conditions.
10.1

Critical Error

At switch on or reboot the PreLOG does a self-checking of its hardware. If any errors are detected, the PreLOG
will not start to log and reports a critical error. The description of these critical errors can be displayed with the
function "PreLOG Critical Error".