3.2. Switching Off
If the UPS is in Normal Mode: Switch off your loads safely. Press the
1.
ON/OFF button briefly. Press the ON/OFF button briefly again to confirm
bypass operation and observe the by-pass and the mains LEDs turn on
(Figure 3.9, Figure 3.10).
The UPS must be operated in bypass mode prior to fully switching
off after normal mode.
If the UPS is in Bypass Mode: Press and hold the ON/OFF button until the
2.
warning beep silences (Figure 3.11). Observe that the display is fully switched
off. Switch off the output, the battery, and the input CBs in respective order
(Figure 3.12).
If the UPS is in Battery Mode: Press and hold the ON/OFF button until
3.
warning beep silences (Figure 3.13). Observe that the display is fully switched
off. Switch off the output, battery, and input CBs in respective order (Figure
3.12).
Page | 14 –
B1 10kVA V1.0.1
Figure 3.9
Figure 3.11
Figure 3.13
Figure 3.10
Figure 3.12