Program Parameters For Operating Mode - Carrier MOTORMASTER 48/50P3 Installation Instructions Manual

48/50p2,p3,p4,p5030-100 low ambient operation motormaster v control accessory 50/60 hz
Table of Contents

Advertisement

PARAMETERS
P01
Line Voltage: 01 = low line, 02 = high line
P02
Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz
P03
Startup mode: flying restart
P04
Stop mode: coast to stop
Standard Speed source: 01 = keypad, 04 = 4-20mA (NO PI), 05 = R22 or R410A,
P05
06 = R134a
P06
TB-14 output: 01 = none
P08
TB-30 output: 01 = none
P09
TB-31 Output: 01 = none
P10
TB-13A function sel: 01 = none
P11
TB-13B function sel: 01 = none
P12
TB-13C function sel: 01 = none
P13
TB-15 output: 01 = none
P14
Control: 01 = Terminal strip
P15
Serial link: 02 = enabled 9600,8,N,2 with timer
P16
Units editing: 02 = whole units
P17
Rotation: 01 = forward only, 03 = reverse only
P19
Acceleration time: 20 sec
P20
Deceleration time: 10 sec
P21
DC brake time: 0
P22
DC BRAKE VOLTAGE 0%
P23
Min freq = 8 Hz ~ 100 – 160 rpm
P24
Max freq
P25
Current limit: (%)
P26
Motor overload: 100
P27
Base freq: 60 or 50 Hz
P28
Fixed boost: 0.5% at low frequencies
P29
Accel boost: 0%
P30
Slip compensation: 0%
P31
Preset spd #1: speed if loss of control signal
P32
Preset spd #2: 0
P33
Preset spd #3: 0
P34
Preset spd 4 default — R22 setpoint. TB12-2 open
P35
Preset spd 5 default — R134a setpoint. TB12-2 closed
P36
Preset spd 6 default
P37
Preset spd 7 default
P38
Skip bandwidth
P39
Speed scaling
P40
Frequency scaling 50 or 60 Hz
P41
Load scaling: default (not used so NA)
P42
Accel/decel #2: default (not used so NA)
P43
Serial address
P44
Password:111
Speed at min signal: 8 Hz; used when PID mode is disabled and 4-20 mA input is
P45
at 4 mA
Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20 mA input is
P46
at 20 mA
P47
Clear history? 01 = maintain. (set to 02 to clear)
P48
Program selection: Program 1 – 12
P61
PI Mode: 05 = reverse, 0-5V, 01 = no PID
P62
Min feedback = 0 (0V *10)
P63
Max feedback = 50 (5V * 10)
P64
Proportional gain = 3.5%
P65
Integral gain = .2
P66
PI accel/decel (setpoint change filter) = 10
P67
Min alarm
P68
Max alarm
LEGEND
NA
— Not Applicable
PI
— Proportional Integral
PID — Proportional Integral Derivative
Table 5 — Program Parameters for the Operating Mode
DESCRIPTION
14
MODE 1
MODE 2
MODE 4
01
02
02
01
01
01
06
06
06
01
01
01
05
05
05
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
02
02
02
02
02
02
01
01
01
20
20
20
10
10
10
0
0
0
0
0
0
8
8
8
60
60
50
125
110
110
100
100
100
60
60
50
0.5
0.5
0.5
0
0
0
0
0
0
57
57
47
0
0
0
0
0
0
24.0
24.0
24.0
12.6
12.6
12.6
0
0
0
0
0
0
0
0
0
0
0
0
60
60
50
200
200
200
60
60
60
1
1
1
111
111
111
8
8
8
60
60
50
01
01
01
01
02
04
05
05
05
0
0
0
50
50
50
3.5
3.5
3.5
.2
.2
.2
10
10
10
0
0
0
0
0
0