CS-G90KE
Operation Details
c.
Anti-Fog Discharge Control
The compressor operating frequency is regulated by outdoor air temperature and operation time to prevent
fog discharged from indoor unit as shown in the table below.
Operation
Time, T (min)
Outdoor air temperature (°C)
Model No.
Note: • Indoor fan is running at Me+ or below.
• After 420 minutes from the start of operation, the operation timer counting is restarted from "0".
d.
High Pressure Control at Minimum Frequency Control
When the outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to
minimum of 33 Hz. Compressor operating frequency will resume to normal when outdoor air temperature
decreases to 37.8°C.
e.
Electrical Components Overheating Protection
When outdoor air temperature is 38.5°C or above and the compressor operating frequency is 25 Hz or above,
total running current set value is reduced (refer to Total Running Current Control) and the operating
frequency is reduced.
The protection control is cancelled when the outdoor air temperature decreases to 37.5°C or compressor
stops.
Compressor operating frequency (Hz)
0 ≤ T < 30
72
30 ≤ T < 90
68
90 ≤ T < 180
57
T ≥ 180
55
less than
24°C
CU-G90KE
83
78
72
70
68
64
57
55
24°C and
less than
above
24°C
CU-G120KE
– 47 –
94
78
70
64
24°C and
above