SYMPTOMS AND POSSIBLE CAUSES - THERMOSTAT VERSION

SYMPTOM
Unit won't cool
Compressor tries to start but won't run
Unit blows breakers
Getting water in enclosure
For additional technical support, contact nVent Equipment Protection at 800-896-2665.
89209668
Clogged fins on coil(s)
Dirty filter
Impellers not running
Compressor not running
Compressor runs, but has bad valves
Loss of refrigerant
Low line voltage at start. Should be +/-10% rated voltage.
Compressor motor stuck
Bad contactor
Bad overload switch
Bad run/start capacitor
Undersized breaker/fuse or not time delayed
Short in system
Drain plugged
Drain tube kinked
Enclosure not sealed (allowing humidity in)
Mounting gasket damaged
© 2022 nVent
POSSIBLE CAUSE
- 37 -