Maintenance; Compressor; Inlet Air Filter; How To Remove, Clean Or Install A New Inlet Air Filter - nvent SPECTRACOOL G52 Instruction Manual

Table of Contents

Advertisement

MAINTENANCE

COMPRESSOR

The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and should
provide years of satisfactory operating service.
Under no circumstances should the access fitting covers be loosened, removed or tampered with.
Breaking of seals on compressor access fittings during warranty period will void warranty on hermetic system.
Recharging ports are provided for the ease and convenience of reputable refrigeration repair service personnel for
recharging the air conditioner.

INLET AIR FILTER

This air conditioner was designed with a dust resistant condenser coil. This allows it to be run filterless in most
applications. The air conditioner is shipped with a filter in place for your convenience. For filterless operation,
simply remove the filter. Should you decide the filter is necessary in your application, regular maintenance to
clean this filter will assure normal operation of the air conditioner. The easily removable inlet air filter is located
behind the front cover. If necessary filter maintenance is delayed or ignored, the maximum ambient temperatures
under which the unit is designed to operate will be decreased.
If the compressor's operating temperature increases above designed conditions due to a dirty or clogged
filter (or plugged condenser coil), the air conditioner's compressor will stop operating due to actuation of the
thermal overload cut-out switch located on the compressor housing. As soon as the compressor temperature
has dropped to within the switch's cut-in setting, the compressor will restart automatically. However the above
condition will continue to take place until the filter or coil has been cleaned. It is recommended that power to
the air conditioner be interrupted intentionally when abnormally high compressor operating temperature causes
automatic shut-down of the unit. The above described shut-down is symptomatic of a clogged or dirty filter, thus
causing a reduction in cooling air flow across the surface of the compressor and condenser coil.

HOW TO REMOVE, CLEAN OR INSTALL A NEW INLET AIR FILTER

RP aluminum washable air filters are designed to provide excellent filtering efficiency with a high dust holding
capacity and a minimum amount of resistance to air flow. Because they are constructed entirely of aluminum
they are lightweight and easy to service. To achieve maximum performance from your air handling equipment, air
filters should be cleaned on a regular basis.
The inlet air filter is located behind the front access cover. To remove filter, push or pull to slide filter out from
either side of the unit. The filter may now be cleaned or a new filter installed.
Cleaning Instructions:
1. Flush the filter with warm water from the exhaust side to the intake side. DO NOT USE CAUSTICS.
2. After flushing, allow filter to drain. Placing it with a corner down will assure complete drainage.
89209668
© 2022 nVent
- 29 -

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents