Carrier 50HE003-006 Installation Instructions Manual page 63

Single-package rooftop electric cooling units with optional electric heat
Table of Contents

Advertisement

Table 35—Humidi-Mizer Adaptive Dehumidification System Sequence of Operation and
THERMOSTAT INPUT
H
Y1
Y2
OAT. < Economizer Set Point
Off
On
On
On
On
On
Off
On
On
On
On
On
Off
On
Off
Off
NOTE: On a thermostat call for W1, all cooling and dehumidification will be off.
LEGEND
OAT --- Outdoor Air Temperature
Fig. 56 --- Separating Coil Sections
4. Remove device holding coil sections together at return end
of condenser coil. Carefully separate the outer coil section
3 to 4 in. from the inner coil section. (See Fig. 57.)
5. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal manner.
6. Secure the sections together. Reposition the outer coil
section and remove the coil corner post from between the
top panel and center post. Install the coil corner and center
posts. Replace all screws.
Condensate Drain
Check and clean each year at the start of the cooling season. In
winter, keep the drain dry or protect it against freeze-up.
Filters
Clean or replace at the start of each heating and cooling season, or
more often if operating conditions require it. Replacement filters
must be the same dimensions as the original filters.
Outdoor- -Air Inlet Screen
Clean the screen with steam or hot water and a mild detergent. Do
not use disposable filters in place of screens.
Step 2 —Lubrication
Compressor
The compressor is charged with the correct amount of oil at the
factory.
System Response — Single Compressor Unit (50HE003- -006, 50HJ004-007)
ECONOMIZER FUNCTION
No
No
Yes
Yes
No
C06046
Economizer
Comp. 1
Subcooling Mode
Normal Operation
Off
On
Off
On
On
On
On
On
Off
On
Fan Motor Bearings
Fan motor bearings are permanently lubricated. No further
lubrication is required.
evaporator-fan motors is required.
Evaporator Fan Belt Adjustment
Inspect evaporator fan belt for wear, proper belt tension, and
pulley alignment as conditions require or at the beginning of each
heating and air conditioning season. Refer to Step 7 - - Adjust
Evaporator Fan Speed for adjustment and alignment procedures.
Step 3 —Condenser- -Fan Adjustment
Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub
setscrews. Adjust fan height as shown in Fig. 57. Tighten
setscrews and replace condenser-fan assembly.
UNIT
003-006 AND 007 (208/230 v)
007 (460 v)
Fig. 57 --- Condenser- -Fan Adjustment
Step 4 —EconoMi$er IV Adjustment
Refer to Optional EconoMi$er IV and EconoMi$er2 section.
Step 5 —Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate (also
refer to Table 1). Refer to HVAC Servicing Procedures literature
available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 minutes
before checking or adjusting refrigerant charge.
No Charge
Use standard evacuating techniques. After evacuating system to
500 microns, weigh in the specified amount of refrigerant. (Refer
to Table 1 and unit information plate.)
63
48HE, HJ UNIT OPERATION
Hot Gas Reheat Mode
Yes
Yes
Yes
No
No
No lubrication of condenser-fan or
FAN HEIGHT (in.) — "A"
2.75
3.50
No
No
No
Yes
Yes
C06138