Triple Evacuation Method; Refrigerant Charge; No Charge; Low Charge Cooling - Carrier 48/50PG C03-14 Operation And Service Manual

Single package rooftop units with comfortlink controls version 5.x and puron (r-410a) refrigerant
Table of Contents

Advertisement

Triple Evacuation Method

The triple evacuation method should only be used when vacuum
pump is capable of pumping down to 28−in. of mercury and
system does not contain any liquid water. Proceed as follows:
1. Pump system down to 28−in. of mercury and allow pump
to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen will be able to diffuse
throughout the system, absorbing moisture.
5. Repeat this procedure. System will then contain minimal
amounts of contaminants and water vapor.

Refrigerant Charge

Amount of refrigerant charge is listed on unit nameplate. Refer to
Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and
Reclamation section for charging methods and procedures. Unit
panels must be in place when unit is operating during charging
procedure.
Puron (R-410A) refrigerant systems should be charged with
liquid refrigerant. Use a commercial type metering device in the
manifold hose.
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R−410A) refrigerant systems operate at higher
pressures than standard R−22 systems. Do not use R−22
service equipment or components on Puron refrigerant
equipment. Gauge set, hoses, and recovery system must
be designed to handle Puron refrigerant. If unsure
about equipment, consult the equipment manufacturer.
NOTE:
Do not use recycled refrigerant as it may contain
contaminants.

No Charge

Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant (refer to unit
nameplate).
NOTE: System charge for units with Humidi-MiZer system is
greater than the system charge of the standard unit.

Low Charge Cooling

Using cooling charging chart (see Fig. 58−79), add or remove
refrigerant until conditions of the chart are met. An accurate
pressure gauge and temperature-sensing device is required.
Charging is accomplished by ensuring the proper amount of liquid
subcooling. Connect pressure gauge to the compressor discharge
service valve. Connect temperature sensing device to the liquid
line between the condenser and the TXV (thermostatic expansion
valve), and insulate it so that ambient temperature does not affect
reading.
To Use the Cooling Charging Chart, Standard Unit
NOTE: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Appendix D.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
Override function to start all outdoor fans.
R410A
R410A REFRIGERA
REFRIGERANT
OUTDOOR FAN
OUTDOOR
FAN MUST
MUST BE
160
160
140
140
Add
dd Charge
Charge if if Above
bove the
the Curve
Curve
120
120
100
100
80
80
60
60
40
40
20
20
150
150
200
200
250
250
300
300
Compressor
Comp
ressor Disch
Discharge
Fig. 58 − Charging Chart — 48/50PG03
R410A RE
R4
OUTDOOR F
R FAN M
N M UST BE OPERATING ON H
16
160
140
14
12
120
Add Cha
harge
ge if Abov
bove the
the Cur urve
100
10
80
80
Rem ove Charge if Be
Re
60
60
40
40
20
20
150
150
200
200
250
250
300
300
Compre ss
ssor Disc
Fig. 59 − Charging Chart — 48/50PG04
Use the temperature and pressure readings, and find the
intersection point on the cooling charging chart. If intersection
point on chart is above line, add refrigerant. If intersection point on
chart is below line, carefully recover some of the charge. Recheck
suction pressure as charge is adjusted.
The TXV is set to maintain between 10 and 15 degrees of
superheat at the compressors. The valves are factory set and cannot
be adjusted. Do not use A TXV designed for use with R-22.
To Use the Cooling Charging Charts, Units With
Humidi−Mizert Adaptive Dehumidification System
NOTE: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Appendix D.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
function (Service Test→COOL→OF.OV) to start all outdoor fans.
88
NT
BE OPERATING
OPERATING ON
ON HIGH
HIGH SPEED
SPEED
Remove
Remo
ve Charge
Charge if if Below
Below the
the Curve
Curve
350
350
400
400
450
450
500
500
550
550
600
600
arge Pressu
Pressure,
re, [p [psig
sig]
REFRI RIGERANT
RANT
N HIGH S
H SPEED
Below the Curve
350
350
400
400
450
450
500
500
550
550
600
600
isc ha rge P re ss
ssure , [psig
sig]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents