PW Series Installation Guide
LED Blink Codes
Commissioning
(PWxxxBP only)
Maintenance
(PWxxxBP only)
Z202882-0X
Page 4 of 4
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
LED Color
Solid Green
Normal operation.
Flashing Green
Low > High; use port swap jumper or bidirectional mode.
Solid Red
Differential pressure is too high; select a higher pressure range.
Flashing Red
Gauge pressure over sensor range; reduce line pressure or replace with a higher range device.
Alternating Green/Red Flash
Sensor input is below sensor range. Verify that the sensor is connected correctly.
1. Close C and D.
2. Open B (null).
3. Open D (bleed or purge).
4. Slowly open A to bleed air from line.
5. Close B, then fully open A.
6. Slowly open C to bleed air from line.
7. Close D, then fully open C.
1. Bleed or purge: see Commissioning step.
2. Equalize pressure: open B.
3. Isolate sensors: close A and C.