Question 9a
Pulse Z1 (Y/N)
Question 9b
Question 9c
Question 10a
Pulse Z2 (Y/N)
Question 10b
Question 10c
Question 11a
Pulse Z3 (Y/N)
Question 11b
Question 11c
Question 12a
Pulse Z4 (Y/N)
Question 12b
Question 12c
Press Y if zone 1 is connected to a pulsed bell output. Question 9c will
appear. If N is pressed, the following appears.
Enter the reporting delay from 1-127 seconds for
Z1 Delay
zone 1. Enter 00 for no reporting delay.
(00-127)
If Pulsed Zone is answered Y, the next question will
Pulse Cnt? (Y/N)
be Pulse Cnt? Input the number of pulses required
(03 - 254)
to place the zone in alarm. Default is (03).
Press Y if zone 2 is connected to a pulsed bell output. Question 10c will
appear. If N is pressed, the following appears.
Enter the reporting delay from 1-127 seconds for
Z2 Delay
zone 2. Enter 00 for no reporting delay.
(00-127)
If Pulsed Zone is answered Y, the next question will
Pulse Cnt? (Y/N)
be Pulse Cnt? Input the number of pulses required
(03 - 254)
to place the zone in alarm. Default is (03).
Press Y if zone 3 is connected to a pulsed bell output. Question 11c will
appear. If N is pressed, the following appears.
Enter the reporting delay from 1-127 seconds for
Z3 Delay
zone 3. Enter 00 for no reporting delay.
(00-127)
If Pulsed Zone is answered Y, the next question will
Pulse Cnt? (Y/N)
be Pulse Cnt? Input the number of pulses required
(03 - 254)
to place the zone in alarm. Default is (03).
Press Y if zone 4 is connected to a pulsed bell output. Question 12c will
appear. If N is pressed, the following appears.
Enter the reporting delay from 1-127 seconds for
Z4 Delay
zone 4. Enter 00 for no reporting delay.
(00-127)
If Pulsed Zone is answered Y, the next question will
Pulse Cnt? (Y/N)
be Pulse Cnt? Input the number of pulses required
(03 - 254)
to place the zone in alarm. Default is (03).