Firecycle III-OH 432d
TONE SILENCE button and press
SYSTEM RESET once (again). The
yellow LED will flash indicating zone
#1 is disabled.
B. To disable subsequent zones, contin-
ue holding the TONE SILENCE but-
ton, and press the ALARM SILENCE
button to select the next zone (the
LED will flash on the zone selected)
or ALARM ACTIVATE button to se-
lect the previous zone. Continue
to holding ALARM SILENCE and
press SYSTEM RESET to disable a
TECHNICAL DATA
selected zone. When disabled, the
yellow LED will flash indicating the
zone is disabled.
4. When desired zones are disabled, re-
lease the TONE SILENCE
ton. The Piezo sounder will sound.
5. To silence the Piezo, press TONE
SILENCE.
6. To re-enable a disabled zone, repeat the
procedure.
Note: If any zone has been disabled, the
Trouble Relay will activate and the System
FIRECYCLE® III-OH CYCLING
DOUBLE INTERLOCKED
PREACTION SYSTEM
Trouble LED will flash. If a zone has been
disabled, an alarm that occurs on that
zone will flash the red zone LED, but will
not sound the Piezo or activate any output
circuit. If both power sources are removed
b u t -
from the system, all zones will be re-en-
abled upon restoration of power. Disable
status is lost.
Refer
also
INSTRUCTIONS provided in current
Viking Technical Data describing individual
components of the Viking Firecycle® III-
OH System.