Troubleshooting
Issue
Unit does not
start.
Unit not cooling
or heating the
room.
Unit display
shows strange
numbers/
characters.
Unit makes
noises.
Water dripping
outside.
Water dripping
inside.
PTAC-SVX002A-EN
Possible Causes
Unit may have become unplugged.
Fuse may be blown.
Circuit breaker may be tripped.
Unit may be OFF or in wall thermostat
mode.
Unit may be in a protection or diagnostic
failure mode. (Refer to the section,
Intelligent Self-checking Control.)
Unit air discharge section is blocked.
Temperature setting is not high or low
enough. Setpoint limits may not allow the
unit to heat or cool the room to the desired
temperature.
Unit air filters are dirty.
Room is excessively hot or cold when unit
is started.
Vent door left open.
Unit may be in a protection of diagnostic
failure mode. (Refer to the section,
Intelligent Self-checking Control.)
Compressor is in time delay mode. There
is a protective time delay (approximately
3 seconds) on starting the compressor
after a power outage (or restarting after it
has been turned OFF) to prevent tripping
of the compressor overload.
Wall sleeve is not installed level.
Resolution
Ensure that the plug is securely in the wall
receptacle.
Replace the fuse.
(a)
Turn ON the unit. The unit shows green
when ON and red when OFF. If the LED is
not lit, there may be a problem with power
or damage to the control.
Ensure that curtains, blinds, or furniture
are not restricting or blocking unit airflow.
Reset to a lower or higher temperature
setting.
Remove and clean filters.
Allow a sufficient amount of time for the
unit to heat or cool the room. Start
heating/cooling early before outdoor
temperatures, cooking heat, or
gatherings of people begin to make the
room uncomfortable.
Close the vent door.
Check the dip switch settings for the
desired comfort level.
Wait approximately three (3) minutes for
the compressor to start.
The unit may be in a diagnostic condition.
(Refer to the section, Intelligent Self-
checking Control.)
The unit may be set for Celsius instead of
Fahrenheit.
Clicking, gurgling, and whooshing sounds
are normal during the operation of the
unit.
If a drain kit has not been installed,
condensation run-off during very hot and
humid weather is normal.
If a drain kit has been installed and is
connected to a drain system, check
gaskets and fitting around the drain for
leaks or clogs.
Wall sleeve must be installed level for
proper drainage of the condensation.
Check that the installation is level and
make any necessary adjustments.
(b)
29