11. Duct heater
In the case of installing a duct heater interlocked with Lossnay, be sure to observe the following:
① Select a duct heater in compliance with local and national laws, ordinances, and standards.
Select a duct heater that has obtained the CE mark.
② Always select a heater that is equipped with a non-self-resetting safety device.
Do not directly supply power from the Lossnay unit to the duct heater. Doing so could cause fire.
③ Install a circuit breaker for the duct heater in compliance with all applicable laws, ordinances, and standards.
④ Install the duct heater separated from the product by a distance of 2 m or more.
Failure to do so may result in equipment damage due to the transmission of residual heat from the heater.
⑤ When using a heater without a temperature control function, select a heater with a capacity that is matched to the air
volume.
⑥ Do not use the heater outside the set air volume.
If the heater's capacity is too larger, this may result in the heater frequently turning ON/OFF.
If the heater's capacity is too small, this may result an inability to heat.
⑦ Ensure that the duct heater and Lossnay are wired and that the Lossnay function settings have been configured, and then
always check operation by trial operation.
■ Maintenance and lifetime
The parts listed below are service parts. It is necessary that the regular check and the regular replacement or the
replacement when it is broken. In addition, expenses for parts and replacement work is charged to customers.
- Motor
- Printed circuit board
- Lossnay core (Around 10 years with maintenance at stated periods.)
- Air filter (Around 5 years with maintenance at stated periods)
SAFTY NOTES
DATE
TYPE
15-Oct-2015
MODEL
NUMBER
※Specification may be subject to change without notice.
CEILING RECESSED LOSSNAY
LGH-200RVXT-E