CHAPTER
Function
2
2.3 Function setting from PZ-61DR-E
2.3.1 Function list
No.
Function
Night-purge setting 4)
*33
Time span for memorizing
The functions indicated with * are newly added or modified from Lossnay LGH-RX5-E series.
Function No.33 is added from LGH-RVXT-E series. And this function is also available for LGH-RVX-E (November 2015 production,
serial No. 2015110001 or later).
6. Night-purge function
6.1 Descriptions of Night-purge function.
<Night-purge starting condition>
No.
Content
1
Lossnay is OFF
2
The time display is between operation
starting time and end time. *1
3
Summer condition judgement
(correspond to any of the following)
Outdoor temperature was detected
more than 17˚C within the last setting
hours at function No. 33. *2
The Lossnay unit is interlocked with City
Multi and operation mode of indoor unit
was "cool" or "dry"
4
Indoor temperature is higher than 22˚C
5
Indoor temperature is 5K higher than outdoor
temperature. *3
*2
The threshold of outdoor temperature can be set to between
15˚C and 30˚C (1K increments). Factory setting is 17˚C. If
the maximum outdoor temperature in the last setting hours at
function No. 33 exceeded this temperature value (threshold),
Lossnay starts the temperature monitoring operation.
*1, *3, *4 and *5 are the same as the technical manual of
LGH-RVX-E.
Setting Data
0
1
2
24 hrs
48hrs
72hrs
( 10 / 14 )
3
4
5
6
-
-
-
-
in the last setting hours at function No.33 was
Revised information
Factory
DIP-SW
setting
No.
7
-
0
N/A
N15HHGT0033
Individual
setting
-