FIRE DAMPER UVS 120H
(Two-Bladed design)
Installation manual
EN

Advertisement

loading
Need help?

Need help?

Do you have a question about the UVS 120H and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Komfovent UVS 120H

  • Page 1 FIRE DAMPER UVS 120H (Two-Bladed design) Installation manual...
  • Page 2: Table Of Contents

    4. INSTALLATION STEPS .......................................7 4.1. Signalling devices (switches) installation instructions for fire dampers UVS-H ................. 11 5. PERIODICAL INSPECTIONS ....................................13 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 3: Fire Damper Design And Dimensions

    6 – spring washer, 7 – handle of the opening device, 8 – microswitch cap, 9 – PUSH button mechanism (replacing part), 10 – screw, 11 – Fuse element 70˚ SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 4 H = 990, H1 = 930, L = 265 1000 H = 1040, H1 = 980, L = 290 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 5: Installation Method Examples

    2. Plaster / mortar (e.g. Knauf MP75L or analogue). 3. Fire damper UVS. Anchor screws (according wall material) B+60mm Opening dimension SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 6: Safety Requirements

    • Any changes or modifications of the fire damper are strictly prohibited, except for using manufacturer’s provided replacement parts. • Qualified staff only are allowed to replace parts or service the fire damper. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 7: Installation Steps

    2. Please consider that fire damper has exposition of the blade into the duct within a certain distance in either direction: H, mm L, mm 1000 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 8 75 mm to the walls, ceiling or other partitions, but it is recommended to leave the access space to main mechanism at least 300 mm. ≥200 ≥75 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 9 Please be advised, that after installation of the damper periodical inspections will be held in accordance with p. 4 and it is necessary to ensure access to the main mechanism of a fire damper. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 10 – only one additional plastic part must be installed. This plastic part comes as a set with the switches. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 11: Signalling Devices (Switches) Installation Instructions For Fire Dampers Uvs-H

    Avoid to fold the plate too hard so it can be broken! scheme using signaling device is shown SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 12 • CONSTRUCTION WASTE OR DUST SHOULD NOT BE LEFT ON THE SURFACES OF THE DAMPER; • ACTUATOR IS DISCONNECTED OR MOUNTED LOOSE ON SHAFT; • WIRES RUN THROUGH THE FIRE DAMPER. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
  • Page 13: Periodical Inspections

    Pass / fail blade drop test Pass End switches indicate blade closing Fire damper left in OPEN position Year of inspection Comments SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...