4. INSTALLATION STEPS .......................................7 4.1. Signalling devices (switches) installation instructions for fire dampers UVS-H ................. 11 5. PERIODICAL INSPECTIONS ....................................13 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
6 – spring washer, 7 – handle of the opening device, 8 – microswitch cap, 9 – PUSH button mechanism (replacing part), 10 – screw, 11 – Fuse element 70˚ SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Page 4
H = 990, H1 = 930, L = 265 1000 H = 1040, H1 = 980, L = 290 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
2. Plaster / mortar (e.g. Knauf MP75L or analogue). 3. Fire damper UVS. Anchor screws (according wall material) B+60mm Opening dimension SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
• Any changes or modifications of the fire damper are strictly prohibited, except for using manufacturer’s provided replacement parts. • Qualified staff only are allowed to replace parts or service the fire damper. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
2. Please consider that fire damper has exposition of the blade into the duct within a certain distance in either direction: H, mm L, mm 1000 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Page 8
75 mm to the walls, ceiling or other partitions, but it is recommended to leave the access space to main mechanism at least 300 mm. ≥200 ≥75 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Page 9
Please be advised, that after installation of the damper periodical inspections will be held in accordance with p. 4 and it is necessary to ensure access to the main mechanism of a fire damper. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Page 10
– only one additional plastic part must be installed. This plastic part comes as a set with the switches. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Avoid to fold the plate too hard so it can be broken! scheme using signaling device is shown SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Page 12
• CONSTRUCTION WASTE OR DUST SHOULD NOT BE LEFT ON THE SURFACES OF THE DAMPER; • ACTUATOR IS DISCONNECTED OR MOUNTED LOOSE ON SHAFT; • WIRES RUN THROUGH THE FIRE DAMPER. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Pass / fail blade drop test Pass End switches indicate blade closing Fire damper left in OPEN position Year of inspection Comments SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...
Page 14
SIA KOMFOVENT Bukaišu iela 1, LV-1004 Riga, Latvia Tel. +371 24 66 4433 info.lv@komfovent.com Fire damper UVS120 H (Two-Bladed design) ∙ Installation manual ∙ 21-01...