SAFETY REQUIREMENTS ..............................15 INSTALLATION STEPS ............................... 16 4.1. Signaling devices (switches) installation instructions ....................19 PERIODICAL INSPECTIONS ............................... 21 SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Steel collar-type montage tool with 3 plates (6 x Ø6 mm holes) – Steel overlay-type montage tool (12 x Ø5 mm holes) – designed designed for walls for ceilings SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 4
Steel collar-type montage tool with 3 plates (6 x Ø6 mm holes) – Steel overlay-type montage tool (12 x Ø5 mm holes) – designed designed for walls for ceilings SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
- fill the gap between wall and casing of the damper with mineral wool - apply a fire stopping coating overlapped at wall for 40 mm. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 6
4. Mineral wool installation 5. Fire stopping coating 6. Installation of the additional gypsum boards SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Dry montage kit consists of: Two С-shape Shield flanges made of 40 mm thick Promatect-MT fire-resistant parts – 1 set material SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 8
Using two ISO 7049 screws [6], join shield flanges [2] to the previously installed metal corners [3]. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Internal face of the square opening must be also coated with 2 mm thick fire-resistant coating with min. fire resistant capacity EI 120 for all installations in a flexible wall SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
- let the plaster or mortar dry completely and remove the mounting accessorize. Installations with main mechanism located above or below the ceiling panel are acceptable. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Positioning of the collar for supposed to be located in the supporting size range construction. Ø100÷315 mm SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 12
Montage collar US-d for d = [355 ÷ 560] mm 6 x Ø6 mm mounting holes For vertical fire damper installation in the wall SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
1, 3, 4, 5 (EN 520) ≥ 100 mm 100 ÷ 315 mm 300 Pa resistant coating SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 14
3 - axis position: horizontal; 4 – min. distance between casings: 200 mm; 5 – min. distance to load-bearing structural elements: 75 mm SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
• Any changes or modifications of the fire damper are strictly prohibited, except for using manufacturer’s provided replacement parts. • Qualified staff only are allowed to replace parts or service the fire damper. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
4. Cover the main mechanism (if delivered uncovered) in the process of damper installation with plastic film or another material to protect it against clogging with construction dust and materials. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 17
Note: for installation of a damper into a wall axle of the blade should be positioned horizontally only! Blade of a damper always has to be placed INSIDE the supporting construction. Main mechanism can be used as a guide to find right damper’s position: SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 18
It is easy to mount end positions switches on fire dampers with plastic actuation mechanism – only one additional plastic part must be installed. This plastic part comes as a set with the switches. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Using an appropriate tool (e.g. pliers), GENTLY fold the metal plate as shown: Avoid to fold the plate too hard so it can be broken! SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 20
• CONSTRUCTION WASTE OR DUST LEFT ON THE SURFACES OF THE DAMPER; • ACTUATOR IS DISCONNECTED OR MOUNTED LOOSE ON SHAFT; • WIRES RUN THROUGH THE FIRE DAMPER. SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Pass / fail blade drop test End switches indicate blade closing Fire damper left in OPEN position Year of inspection Comments SIA KOMFOVENT reserves the right to make changes without prior notice Fire damper UVA60 H / UVA120 H installation manual 21-01...
Page 22
SIA KOMFOVENT Bukaišu iela 1, LV-1004 Riga, Latvia Tel. +371 24 66 4433 info.lv@komfovent.com Fire damper UVA60 H / UVA120 H installation manual 21-01...