8. Requirements for Ambient Conditions During Use
Normal ambient conditions for use of Resilient Power Control Module (RPCM) are the following:
operation range of ambient temperature is 0-40°С;
operation range of relative humidity is 45-85% (non-condensing);
operation range of altitude is 0-2000m.
The surrounding environment is non-explosive, does not contain a considerable amount of
conductive dust, vapors, aggressive gases in concentrations that harmfully affect RPCM components
and materials.
WARNING! The maximum range of temperature fluctuation during storage is 20°C per hour.
Storage temperature is from -20 to 60°C. Prior to activating RPCM, it is necessary to allow the
device time of not less than 24 hours to adapt to the new conditions. Physical installation of RPCM
may continue during this acclimatization period. If there is condensation even after the 24-hour
period, it will be necessary to wait until the specified norms have been reached before you can
activate the system.
9. Starting to Operate
Receiving an IP address
IP address is obtained by default via DHCP. If DHCP server is unavailable, RPCM will obtain IP
through Automatic Private IP Addressing (APIPA) thanks to Zero Configuration.
When this method of configuring network addresses is used, IP ranging from 169.254.xxx.xxx,
Netmask 255.255.0.0 (CIDR standard — 169.254.0.0/16) are automatically assigned.
Determining the IP or MAC address
To find out the IP address, you will need to press the bottom button 3 times in succession (press 4
times for the MAC address. Before pressing the next time, you will need to wait for a reaction
to the previous press).
When you press the first time, a running message regarding the electric current level (for example
«25Amps») will be displayed. Only numerical figures will be displayed after 5 seconds.
When you press the second time, the power level will be displayed also as a running message. Only
numerical figures will be displayed after 5 seconds.
When you press the third time, RPCM will switch over to IP address display mode.
When you press the fourth time, the MAC address will be displayed.
Reset to Factory Settings
To reset the device, hold the top button for this RPCM module. For example 1 of 3 on the front
panel for 20 seconds.