NOTE: Before entering the Setup mode to make changes, the user should fill out the
Setup Mode Selection Table (Section 3.9). This aids the user during the selection
process in the Setup mode.
The Password, the High & Low Alarm set points and the Calibration Level options offer
the operator more than two choices. While these options are being selected, pressing the
Mode button repeatedly sequences the display to the next available choice for that
option.
To enter the Setup Check mode:
1. Press and hold the Mode button until the SETUP LED begins flashing (about
twenty seconds).
2. When the SETUP LED is flashing, release the Mode button to enter the Setup
Check mode
To enter the Setup mode:
1. Press and hold the Mode button until the SETUP LED begins flashing (about
twenty seconds
2. Continuing to press and hold the Mode button until the SETUP LED stops
flashing (about five seconds more).
3. When the SETUP LED stops flashing and stays on, release the Mode button and
the unit enters the Setup mode.

3.7.1 Entering the Password

This option applies to the Setup mode only:
If the Password option is enabled, the right digit of the display is blank and a "0"
appears in the left digit on the display. Press the Mode button until the first
number of your password displays, and then wait about five seconds.
The left digit of the display blanks out and a "0" appears in the right digit on the
display. Press the Mode button until your correct password number displays,
then wait about five seconds. If the password is correct the unit proceeds to the
Password Enabled/Disabled option. If the password is incorrect the user cannot
proceed and the unit returns to the normal operating mode. Once in the operating
mode the user may re-enter the Setup Mode. The factory default password is 00.

3.7.2 High Alarm Options

Next, the High LED is flashing while the energized/de-energized option displays. This
option is available for discrete relay configuration only. The display indicates the current
selection, (En or dE). Press the Mode button to toggle the selection. De-Energized (dE)
is the factory default for this selection.
The High LED on the front panel flashes while the latching/non-latching option displays.
The display indicates the current selection, (nL or LA). Press the Mode button to toggle
the selection. Latching (LA) is the factory default for this selection.