Calibration Check Mode; Figure 7: Portable Purge Calibrator - General Monitors 580A Instruction Manual

Two channel control module combustible gas applications
Table of Contents

Advertisement

NOTE: A channel's sensor detects a gas concentration in excess of an alarm set point.
The associated alarm outputs will activate. After a few moments, the gas
concentration drops below the alarm set point. If the alarm outputs are latched,
the operator can press the Reset button and the latched alarm outputs will return
to their normal (safe) state.
3.4

Calibration Check Mode

To perform a calibration check, use the following procedure:
Place the cup from the portable purge calibrator over the sensor.
NOTE: The Calibration Check mode cannot be entered if the unit is in alarm.
1. Enter the Calibration Check mode by pressing and holding the Mode button until the
CAL LED flashes (about ten seconds). The unit displays the calibration level. When
the CAL LED flashes, release the Mode button. The channel is now in the Calibration
Check mode.
2. When the Mode button is released, the display flashes a pair of bars (--) for about ten
seconds. After that "C1" or "C2" displays for a short time indicating which channel is
being checked. The channel's LED is flashing. To select another channel press the
Channel/Select button.
3. When the display flashes digits, for example "0", apply the test gas to the sensor
(open the ON/OFF valve on the cylinder) and wait a few seconds. The display begins
to go up scale as the sensor sees the gas. If no gas is applied, the unit returns to the
normal operating mode after 6 minutes.

Figure 7: Portable Purge Calibrator

17
Model 580A