Appendix; A Commissioning Checklist; B Troubleshooting - Vaillant armoMAG 4/1 G Series Installation And Maintenance Instructions Manual

Table of Contents

Advertisement

Appendix

Appendix
A
Commissioning checklist
No.
Procedure
1
Checking the water filter
2
Check the starting water flow rate
before start-up
3
Starting up the product
4
Check the entire gas route for tightness
5
Check the entire water route for tight-
ness
6
Checking that the flue gas sensor
works correctly
7
Measuring the chimney draught
8
Checking combustion
9
Checking the gas flow pressure
10
Switching off the product and switching
it back on again
11
Setting the domestic hot water function
12
Handing over the operating instructions
to the customer
B
Troubleshooting
Symptom
The product does not work. The
LED does not light up.
The product cannot be started
up. The LED flashes red for up
to ten minutes after water is
drawn.
The product switches off during
operation. The LED flashes red.
22
Comment
Check for availability.
The water flow rate must not exceed
the maximum value.
Use leak detection spray or a leak
detector.
Carry out a visual check.
See section "Checking that the flue gas
sensor works correctly".
The maximum draught must not ex-
ceed 15 Pa. If the draught is too great,
the chimney draught must be restricted
using suitable measures.
Check for flue gas exit.
Target value for nominal heat input:
Only carry out the measurement after
ten minutes of normal operation.
Natural gas: CO 200 ppm
Liquefied petroleum gas: CO
300 ppm
See section "Checking the gas flow
pressure".
Possible cause
The water pressure is too low.
The gas supply is interrupted.
There is air in the gas supply
line.
Fault in the ignition device
The servomotor is defective.
The gas supply is interrupted.
There is air in the gas supply
line.
Ionisation flow too low.
The flame detector is defective.
Required tool
Leak detection spray/leak detector
Vaillant flue gas restrictor
Analyser for chimney draught
Dew point hygrometer
CO analyser
U-tube or digital manometer
Measure
1.
Ensure that the cold-water isolation valve is open.
2.
Check the water valve. (→ Page 18)
1.
Secure the gas supply.
2.
For liquefied petroleum gas: Replace an empty gas cylinder
with a full one.
3.
Ensure that the isolation valve on the gas connection is
open.
Open and close the water tap several times in order to remove
air from the gas supply.
1.
Check the cable connection for the plug contact.
2.
Replace the electrodes.
Replace the servo valve.
1.
Secure the gas supply.
2.
For liquefied petroleum gas: Replace an empty gas cylinder
with a full one.
3.
Ensure that the isolation valve on the gas connection is
open.
Open and close the water tap several times in order to remove
air from the gas supply.
Check the ionisation flow.
1.
Check the cable connection for the plug contact.
2.
If required, replace the monitoring electrode.
Installation and maintenance instructions atmoMAG 0020271929_00