Carrier RHW036-060 Installation Instructions Manual page 31

Table of Contents

Advertisement

MENU
PARAMETER
VENTMIN L
VENTMIN M
VENTMIN H
ERV OAT SP
††
EXH1 SET
SETPOINTS
(CONT)
EXH1 L SET
EXH1 M SET
EXH1 H SET
EXH2 L SET
EXH2 M SET
EXH2 H SET
INSTALL
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
SYSTEM
SETUP
FAN CFM
AUX1 OUT
OCC
FACTORY DEFAULT
527 01 2701 00
Table 9 — W7220 Menu Structure* (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
3.7 V
2 to 10 Vdc
3.4 V
2 to 10 Vdc
2.8 V
2 to 10 Vdc
32°F
0 to 50°F
increment by 1
50%
0 to 100%
65%
0 to 100%
60%
0 to 100%
50%
0 to 100%
80%
0 to 100%
77%
0 to 100%
75%
0 to 100%
01/01/17
N/A
F
F or C
CONV
Conventional or
HP
W
SD/W or HP(O)/
HP(B)
2 speed
1 speed
2 speed
2SP H/C
3 speed
5000cfm
100 to 15000 cfm;
increment by 100
NONE
NONE
ERV
EXH2
SYS
INPUT
INPUT or
ALWAYS
NO
NO or YES
Specifications subject to change without notice.
DCV MINIMUM DAMPER POSITION AT LOW SPEED. Only displays
if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF using 2
speed with 1 heat and 1 cool then set for HEATING ventilation. If
using 3 speed with 1 heat and 2 cool then set for LOW SPEED
COOLING
DCV MINIMUM DAMPER POSITION AT MEDIUM SPEED. Only
displays if unit is set for 3 speed with 1 heat and 2 cool. Set for
HEATING ventilation.
DCV MINIMUM DAMPER POSITION AT HIGH SPEED. Only
displays if unit is set for 2 speed or 3 speed with 1 heat and 2 cool. IF
using 2 speed with 1 heat and 1 cool then set for COOLING
ventilation. If using 3 speed with 1 heat and 2 cool then set for HIGH
SPEED COOLING ventilation
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR
TEMPERATURE SETPOINT
Only displayed when AUX1 O = ERV
Exhaust fan set point for single speed units. Based on OA Damper
position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT LOW SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST POINT 1 SETPOINT AT MEDIUM SPEED. Only displays
if unit is set for 3 speed with 1 heat and 2 cool. Based on economizer
OA damper position to activate power exhaust.
EXHAUST FAN 1 SETPOINT AT HIGH SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT LOW SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT MEDIUM SPEED. Only displays if
unit is set for 3 speed with 1 heat and 2 cool. Based on economizer
OA damper position to activate power exhaust.
EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3
speed with 1 heat and 2 cool. Based on economizer OA damper
position to activate power exhaust.
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump input
from thermostat or controller.
See Menu Note 4.
In CONV mode:
SD + Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must program CONV mode for
W. Shutdown is not available in 2-speed fan mode. See Menu Note 4.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
Sets the economizer controller operation based on 1 speed, 2 speed,
2 speed heat/cool (2SP H/C), or 3 speed supply fan.
NOTE: Multi-speed fan options also need Heat (W1) programmed in
AUX 2 In. See Menu Note 4.
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVAL ENA = AUTO
The value is found on the nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
NONE = not configured (output is not used)
ERV = Energy Recovery Ventilator
EXH2 = second damper position relay closure for second exhaust fan
SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac), the 24
vac is input "INPUT" to the OCC terminal. If no occupancy output from
the thermostat then change program to "ALWAYS" OR add a jumper
from terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD will
briefly flash YES and change to NO but all parameters will change to
the factory default values.
NOTE: RECHECK AUX2 IN and FANTYPE for required 2-speed
values.