Installation sequence

Making the hydraulic connections

Connect heating water flow and heating water return at the heat pump

!
Please note
Mechanically loaded hydraulic connections lead
to leaks, vibration and appliance damage.
Connect supplied connecting hoses (bends)
so that they are free of load and torque stress.
To prevent transmission of any vibration, the
connecting hoses must not contact any other
components.
2.
2x
1.
3.
A
B
C
Fig. 8
Heating water return
A
Heating water flow
B
Hydraulic connection set (accessory)
C

Connect heating circuits and DHW cylinder in the building

1. Equip the secondary circuit on site with an expan-
sion vessel and safety assembly (in accordance
with EN 12828).
Fit the safety assembly to the on-site line in the
heating water return.
2. Connect secondary lines to the lines of the
hydraulic connection set (accessory).
!
Please note
Mechanically loaded hydraulic connections
lead to leaks, vibration and appliance dam-
age.
Connect on-site lines so that they are free of
load and torque stress.
16
A
B
4.
Note
The connecting hoses can be shortened.
Completely encase connecting hoses in the supplied
thermal insulation.
!
3.
Please note
Leaking hydraulic connections lead to appli-
ance damage.
Check the tightness of the internal and on-
site hydraulic connections.
In the event of leaks, drain off liquid via the
drain valve. Check the seating of seal
rings. Always replace displaced seal rings.
Observe information regarding filling and venting:
See page 51.
4. Thermally insulate pipes inside the building.
5. Connect the drain hose to the safety valve.
Connect the drain hose to the public sewage sys-
tem with a fall and a pipe vent.