Econar GeoSurce Vara 2 Plus GV Series Lnstallation And Operating Lnstructions page 8

Vertical and horizontal forced air
Table of Contents

Advertisement

viscous
at
low
temperatures and cannot be
pumped
through
the earth
loop.
Insufficient
amounts
of
antifreeze
may result
in
afreeze rupture
of
the
unit,
and can cause
unit
shutdown problems during
cold
weather operation
(when
the heat
pump
experiences the
longest run
time)
due
to loop temperatues
falling
below
the freeze
protection
of
the antifreeze.
Flow
rate
requirements
for
closed
loops
are
higher than
open
loop
systems because
water temperatures supplied to
the heat
pump
are
generally
lower
(see
Table
3).
From
2.5 to
3.0
gallons
per
minute (GPM)
per ton
are
required
for
proper operation
of
the heat
pump
and the
earth
coupled
heat exchanger.
Table
3
-
Side
Flow
Rates
*Cupro-Nickel Well
Water
Coil
Pressure/Temperature
(P/T) ports
(ECONAR
part number
70-0450)
must be
installed
in
the
entering
and
leaving
water lines
of
the heat
pump on
a
closed
loop
system (see
Figure
2). A
thermometer
can be
inserted
into
the
P/T
ports to
check
entering
and
leaving wator temperafures.
A
pressure gauge can also be
insefied
into
these
P/T ports to
determine
the pressure
differential
between
the
entering
and
leaving
water.
This
pressure
differential
can then be
compared to
the
specification
data on each
particular
heat
pump to determine
the
flow
rate
of
the system.
A
PumpPAKrM that is
individually
sized
for
each
application
can
supply pumping requirements
for
the
earth
loop
fluid.
The PumpPAKrM
can also be used
to
purge
the
loop
system. The PumpPAKrM is wired
directly
to
the
contactor
and operates
whenever
the
compressor
runs
(see
Electrical
Diagram - Figure
4). If
a
PumpPAKrM
is
not
used,
a
separate
pump
can be used
which
is energized
with
a
pump relay (note: electrical
code
will
require
a
fused
disconnect
for
pumps other
than
PumpPAKsrM).
Filling
and
purging
a
closed
loop
system are
very
important
steps
to
assure
proper
heat
pump operation.
Each loop
must be
purged
with
enough water
flow
to
assure
a
two
feet per
second
flow
rate
in
each
circuit
on
the
loop.
This
normally
requires a
1/z
to
3
HP high
head
pump to circulate
fluid
through
the
loop to remove
all
the
air out
of
the
loop
and
into
a
purging
tank. Allow
the
pump
to
run
10
to
15
minutes after
the
last air bubbles
have been
removed.
Enough antifreeze
must be added
to
givefreeze protection
to
15T
betow
the
minimum loop
design
temperature.
This
amount should
be
calculated
and added
to
the
loop
after purging is
complete.
After
antifreeze
has
been
installed,
a
solution
sample
should
be measured
with
a
hydrometer, refractometer or any other device to
determine
the
actual freezing point. Remember that
an
inadequate
antifreeze
level
will
lock
the heat
pump out
on
low
pressure
during wintertime
operation.
The purge pump
can be used
to pressurize
the system
to
an
initial
static pressure
of
30-40
psi.
Make
sure the
system
is
at
this
pressure
after
the
loop pipe
has
had
enough
time
to sfretch. In
order to achieve
the 30
to 40
psi
initial
pressure, the
loop may
need
to
be
pressurized to
60 to
65
psi.
This
static pressure
will
fluctuate
from
heating to
cooling
season,
but the
static pressure
should
always remain
above 20
psi
so
circulation
pumps
do
not
cavitate and air
cannot be
pulled into
the
system.
EFor
information
regarding
earth
loop
installations contact
your
local
loop installer,
ECONAR distributor
or
GeoRep.
B.
Open Loop
Applications
An
open system gets
its
name
from
the open
discharge
of
water after
it
has
been used
by
the heat
pump. A
well
must
be
available that
can
supply
all of
the
water
requirements
(see
Table
3)
of
the heat
pump along
with
any
other
water
requirements drawing
off
that
same
well.
The
well
must be capable
of
supplying
the heat
pump,s
required
flow
rate
for
up to
24 hours
per day on
the
coldest
winter
day.
Figure
3 shows the necessary
components
for
water
piping of
an open
system. First,
a
bladder type
pressure
tank
with
a
"draw down" of
at
least
lYz
times
the
well
pump capacity must
be
installed
on the
supply
side
of
the
heat
pump.
Shut
off
valves
and
boiler
drains
on the
entering
and
leaving water lines
are necessary
for future
maintenance issues.
A
screen
strainer
is
placed
on the
supply
line with
a
mesh size
of
40 or 60
and enough
surface
area
lo
allow for
particle
buildup
between
cleanings.
Pressure/Temperature
@iT)
ports
are
placed
in
the
supply
and discharge
lines
so
that thermometers or
pressure
gauges can be
inserted
into
the
water
stream.
On
the
well
water discharge
side
of
the heat
pump,
a
flow
control
valve must
be
mounted next to
the heat
pump to
regulate
the
maximum
water
flow
through
the
unit. A
solenoid valve is then installed
and
wired
to
the accessory
plug (PA)
on the
controller of
the heat
pump.
This
valve
will
open when
the
unit
is
running
and
close when
the
unit stops.
A
visual
flow
meter is
then
installed to
allow
visual inspection
of
the
flow
requirements.
The
flow
meter
can also be
useful
in
determining when
maintenance
is
required
(if
you can't
read the
flow,
cleaning is required,
see
Water
Coil
Maintenance).
6
GV/GH
38
|
S
2.8
5
2.6*
GV/GH
48
I
tr
5.2
6
3.0*
GV/GH
s8
|
r:
7.5
8
6.0*

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents