Faults / Solutions

Here below you can find some causes and the possible solutions
for some problems that could cause a failure to start or incorrect
operation of the burner.
A fault usually makes the lockout led signal which is situated in-
side the reset push-button of the control box.
Faults
The burner does not
start when there is heat
demand.
The burner goes into
lockout mode before or
during the pre-purging or
pre-heating.
Burner runs normally in
the pre-purge and igni-
tion cycle and locks out
after about 5 seconds.
Burner starts with an ig-
nition delay.
The manufacturer cannot accept responsibility for
any damage to persons, animals or property due
to error in installation or in the burner adjustment,
or due to improper or unreasonable use or non
WARNING
observance of the technical instruction enclosed
with the burner, or due to the intervention of un-
qualified personnel.
20141254
Possible cause
Lack of electrical supply.
The flame sensor sees an extrane-
ous light.
The connections in the control box
are wrongly inserted.
The heater is broken.
The flame sensor sees extraneous
light.
The flame sensor is dirty.
The flame sensor is faulty.
Flame moves away or fails.
The ignition electrodes are wrongly
positioned.
Air output is too high.
Nozzle dirty or worn.
Faults / Solutions
When lockout lamp comes on the burner will attempt to light only
after pushing the reset button. After this if the burner functions
correctly, the lockout can be attributed to a temporary fault that is
not dangerous.
Otherwise, if the lockout persists the cause of the fault should be
sought and the solutions shown in Tab. K put into effect.
Fault diagnostics Solutions
OFF
OFF
0,5 sec ON
2,5 sec OFF
RED
Steady ON
OFF
32
GB
Check presence of voltage in the L - N the pin
plug.
Check the conditions of the fuses.
Check that safety thermostat is not in lockout.
Eliminate the extraneous light.
Check and connect all the plugs and sockets
properly.
Replace them.
Eliminate the extraneous light.
Clear it.
Replace it.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
Check the coil of solenoid valve.
Adjust them according to the instructions of this
manual.
Set the air output according to the instructions of
this manual.
Replace it.
Tab. K