S&P ECOWATT PLUS CRHB 400 N Manual page 34

Table of Contents

Advertisement

Available languages

Available languages

Modbus
Register
adress
30043
S_ALARM_1
30044
S_YEAR_ALARM_1
30045
S_MONTH_ALARM_1
30046
S_DAY_ALARM_1
30047
S_HOUR_ALARM_1
30048
S_MINUTES_ALARM_1
30049
S_SECONDS_ALARM_1
30050
S_ALARM_2
30051
S_YEAR_ALARM_2
30052
S_MONTH_ALARM_2
30053
S_DAY_ALARM_2
30054
S_HOUR_ALARM_2
30055
S_MINUTES_ALARM_2
30056
S_SECONDS_ALARM_2
HOLDING REGISTERS
Modbus
Register
adress
Modbus configuration
40001
Adress
40002
Baud rate
40003
Parity
Resets
40004
Factory_Reset
40005
Reset_Alarms_Count
40006
Full_Reset
General configuration
40009
Vreg_Limit_min
40010
Vreg_Limit_max
40011
Taco_pulses_out
34
Data type
Range
16 BITS
0 – 1
16 BITS
18 – 999
16 BITS
1 – 12
16 BITS
1 – 31
16 BITS
0 – 23
16 BITS
0 – 59
16 BITS
0 – 59
16 BITS
0 – 1
16 BITS
18 – 999
16 BITS
1 – 12
16 BITS
1 – 31
16 BITS
0 – 23
16 BITS
0 – 59
16 BITS
0 – 59
Data
Range
type
CRHB-400 N
ECOWATT
PLUS
16 BITS
1 – 247
1
16 BITS
0 – 3
2
16 BITS
0 – 2
0
16 BITS
0 – 65535
0
16 BITS
0 – 65535
0
16 BITS
0 – 65535
0
16 BITS
0 – 10000
1500
16 BITS
0 – 10000
10000
16 BITS
0 – 10
1
Description
Last IAQ alarm:
0: No alarm
1: AN1 IAQ alarm
2: AN2 IAQ alarm
3: AN3 IAQ alarm
Year of last IAQ alarm
Month of last IAQ alarm
Day of last IAQ alarm
Hour of last IAQ alarm
Minute of last IAQ alarm
Second of last IAQ alarm
Second to last IAQ alarm:
0: No alarm
1: AN1 IAQ alarm
2: AN2 IAQ alarm
3: AN3 IAQ alarm
Year of second to last IAQ alarm
Month of second to last IAQ alarm
Day of second to last IAQ alarm
Hour of second to last IAQ alarm
Minute of second to last IAQ alarm
Second of second to last IAQ alarm
Default
CRVB-400 N
CRHB-450 N
CRVB-450 N
ECOWATT
ECOWATT
ECOWATT
PLUS
PLUS
PLUS
1
1
2
2
2
0
0
0
0
0
0
0
0
0
0
0
0
1500
1500
1500
10000
10000
10000
1
1
1
Description
1
Modbus channel
Transmission speed
0: 4800bps
1: 9600bps
2: 19200bps
3: 38400bps
Transmission parity
0: EVEN
1: ODD
2: NONE
If parity NONE, 2 bits stop as
default. If not, 1 bit stop
Back to factory settings
1234: Reset factory settings
Alarm count reset
independently
2345: Motor alarm count
2456: IAQ alarm count
To reset all
3456: Full reset
Minimum 0-10 voltage
tension to the motor (mV)
Maximum 0-10 voltage
tension to the motor (mV)
Pulses by motor revolution

Advertisement