WIRING AND CONNECTIONS MOUNTING INSTRUCTIONS IN STEPS OPTIONAL MOUNTING INSTRUCTIONS OPERATING INSTRUCTIONS MENU STRUCTURE 7-SEGMENT DISPLAY INDICATION VERIFICATION OF THE INSTALLATION INSTRUCTIONS TRANSPORT AND STORAGE WARRANTY AND RESTRICTIONS MAINTENANCE MIW-RDCV-EN-003 - 15 / 10 / 2020 2 - 13 www.sentera.eu...
In case there are any questions that are not answered, please contact your technical support or consult a professional. MIW-RDCV-EN-003 - 15 / 10 / 2020 3 - 13 www.sentera.eu...
CONTROLLER PRODUCT DESCRIPTION The RDCV series are residential HVAC controllers used to control EC fans, actuators, lighting or other applications with an analogue (0—10 VDC / 0—20 mA / PWM) signal. They feature a wide supply voltage range 110—230 VAC ±10 % / 50—60 Hz and a variable control output signal between an adjustable minimum and maximum level.
Precautions”. Then proceed with the following steps: For inset mounting Disconnect the power supply. Remove the frame cover of the enclosure and take the RDCV controller out, so that it can be easily connected. Do the wiring according to the wiring diagram (see Fig. 1).
Page 7
GND terminal should NOT BE CONNECTED to other units on the network or via the CNVT‑USB‑RS485 converter. This may cause permanent damage to the communication semiconductors and / or the computer! MIW-RDCV-EN-003 - 15 / 10 / 2020 7 - 13 www.sentera.eu...
The EC motor will run at maximum speed. Press the button for 4 seconds until the display shows a decimal point ‘.’. The RDCV is now in Stand-by mode, the output is 0, and the motor will stop. If this is not the case, check the connections.
Page 9
Modbus RTU in order to operate and control the environment based on the information received by the sensor. If no sensor is connected, the display will show “...” and the RDCV will not work. The sensor needs a few seconds in order to take samples from the environment.
Page 10
(percentage) by pressing the button. NO T E In manual mode, the RDCV is a “slave” device. This means that eventually, the output value can be overwritten by a Building Management System. MIW-RDCV-EN-003 - 15 / 10 / 2020 10 - 13 www.sentera.eu...
SEttings baudrate – parity – NBT baudrate Decrement go To bootLoader value RESET To DEFAuLT PRESS to return PRESS for 8 s MIW-RDCV-EN-003 - 15 / 10 / 2020 11 - 13 www.sentera.eu back to the table of contents...
Output value in working mode Digits with a point Parameter value in setting mode Indication of output steps Toggled with output value by pressing MIW-RDCV-EN-003 - 15 / 10 / 2020 12 - 13 www.sentera.eu back to the table of contents...
In case of heavy pollution, clean with a non-aggressive product. In these circumstances the unit should be disconnected from the supply. Pay attention that no fluids enter the unit. Only reconnect it to the supply when it is completely dry. MIW-RDCV-EN-003 - 15 / 10 / 2020 13 - 13 www.sentera.eu...