WARNING: Risk of Explosion, Fire, or
Electric Shock. Label all wires before they are
disconnected when replacing or servicing the G93.
Wiring errors can cause improper or dangerous
operation and may result in an explosion, fire, or
electric shock leading to severe personal injury or
death.
Field repairs must not be made to the G93 valve. If
the thermocouple meets the output listed in Table 1
and the valve does not function, replace the entire
valve. Any attempt to repair this assembly voids the
manufacturer's warranty. For a replacement valve,
contact the original equipment manufacturer or the
nearest BASO Gas Products distributor.
Accessories
Table 3: G93 Gas Valve Conversion Kits
Part
Regulator
Number
Type
Y71GF-3
Bottom Adjust
Y71GF-4
Top Adjust
Y71QH-2
Top Adjust
Y71QH-3
Bottom Adjust
Y71AA-5
Top or
Bottom Adjust
Figure 7: SVC200 Wire Connect DIN
Type Connector
Figure 8: SVC210 Conduit 1/2 NPT
DIN Type connector
©
2018 BASO Gas Products
Part No. BASO-INS-G93MODELREVB, Rev.-
Gas
Conversion
Natural Gas to LP Gas
Natural Gas to LP Gas
LP Gas to Natural Gas
LP Gas to Natural Gas
Non-Regulation
G93 Model Rev. B Series BASOTROL® Combination Automatic Gas Valve

Maintenance Schedule

Preventive maintenance programs are an important
part of maintaining optimum and safe function of your
BASO products. Commercial cooking and other
heating equipment can be a heavy cycling demand on
gas safety controls.
The maintenance programs should include frequent
checkout of the gas controls. Review the procedure as
described in the setup and adjustments and check for
leakage section of the instructions.
Exposure to water, chemicals, dirt, heat and grease
can all contribute to premature shut down of the gas
controls.
The frequency of the maintenance must be determined
by the appliance manufacturer where the controls are
installed and the end user for each individual
application.
Things to consider when determining a preventive
maintenance program:
Number of cycles a gas control will see
annually (more than 20,000 cycles). The gas
control should be checked monthly.
Gas controls used less than 20,000 cycles
should be checked before every shutdown and
restart process.
Heavy grease, high heat, wash down
exposure, corrosive environment areas should
be checked with a higher frequency to prevent
premature shutdown from rapid deterioration.
Simply doing a scheduled maintenance program will
help remove the chances of a costly unexpected
shutdown.
Never try to repair or replace a gas control unless you
are a authorized licensed gas contractor as this will
void the manufactures warranty. In all cases, use an
authorized licensed gas contractor for any gas control
replacement.
7