Product Introduction; Abbreviations; Leds - Grundfos CIM 040 TTL Installation And Operating Instructions Manual

Table of Contents

Advertisement

Available languages

Available languages

2. Product introduction

CIM 040 is a TTL adapter module placed in a CIU
box and designed for communication with a
controller.
The module is an add-on to the existing CIU setup
and cannot work as a stand-alone unit.
6
5
1
Fig. 1
CIM 040
Pos. Description
1
TX TTL to CIM 040
2
RX TTL to CIM 040
3
Ground connection from the controller
4
+5 VDC from the controller
LED1.
5
Green light indicates connection to the
controller.
LED2.
6
Green light indicates connection to the
controller.
4
2
3
4

2.1 Abbreviations

CIM
Communication interface module
CIU
Communication interface unit
CU
Control unit
LED
Light-emitting diode
GND
Ground connection
SELV
Separated or safety extra-low voltage
Separated or safety extra-low voltage
SELV-E
with earth
TTL
Transistor to transistor logic

2.2 LEDs

The module has two LEDs. See fig. 1.
Green status LED (LED2) for communication
between CIM 040 and the CIU box.
Green status LED (LED1) for communication with
the controller.
LED1
Status
Description
No +5 V TTL supply from the
Off
controller.
Permanently
Connection, but no ongoing
green
communication with the controller.
Flashing
Communication with the controller.
green
LED2
Status
Description
Off
No +5 V supply from the controller.
Permanently
Connection, but no ongoing
green
communication with the CIU box.
Flashing
Ongoing communication with the
green
controller.
During startup, there may be a delay of up
Note
to 30 seconds before LED2 shows the
actual status.