Napoleon CONTINENTAL W175-0159 Instructions
Napoleon CONTINENTAL W175-0159 Instructions

Napoleon CONTINENTAL W175-0159 Instructions

Fuel conversion for models bgd36/bcdv36, bgd36cf/bcdv36cf, bgnv36/bcnv36

Advertisement

Available languages

Available languages

Quick Links

INSTALLER: THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOME OWNER.
CHECK THE BOXES TO INDICATE THAT THE CORRESPONDING STEPS HAVE BEEN COMPLETED.
W175-0159, Natural Gas to Propane
(BGD/BCDV36/36CF,BGNV/BCNV36)
REGULATOR ASSEMBLY
#56
BURNER ORIFICE
CONVERSION DATA LABEL
PILOT INJECTOR
This conversion kit shall be installed by a qualifi ed service agency in accordance with the manufacturer's
instructions and all applicable codes and requirements of the authority having jurisdiction. If the
information in these instructions is not followed exactly, a fi re, explosion or production of carbon monoxide
may result causing property damage, personal injury or loss of life. The qualifi ed service agency is
responsible for the proper installation of this kit. The installation is not proper and complete until the
operation of the converted appliance is checked as specifi ed in the owner instructions supplied with the kit.
WARNING: Failure to position the parts in accordance with these
diagrams or failure to use only parts specifi cally approved with
this appliance may result in property damage or personal injury.
CAUTION: The gas supply shall be shut off prior to disconnecting
the electrical power, before proceeding with the conversion.
1. Open the glass viewing door and remove the log set.
LOG SUPPORT SCREWS
BURNER SCREWS
2. Remove the 3 screws securing the burner to the log support.
3. Remove the log support by removing the 4 screws from the fi rebox
back.
BURNER BRACKET SCREWS
4. Remove the burner by removing the screw from each side of the
burner.
BURNER ORIFICE
W415-0971 / 11.17.10
FUEL CONVERSION FOR MODELS
BGD36/BCDV36, BGD36CF/BCDV36CF,
BGNV36/BCNV36
These kits are for use at altitudes of 0 to 4500 feet.
1
1
1
1
PILOT ASSEMBLY
W175-0164, Propane to Natural Gas (BGD/BCDV36/36CF)
W175-0280, Propane to Natural Gas (BGNV/BCNV36)
REGULATOR ASSEMBLY
(IN KIT W175-0164)
#47
BURNER ORIFICE
(IN KIT W175-0280)
#48
BURNER ORIFICE
CONVERSION DATA LABEL
PILOT INJECTOR
5. Using a deep socket wrench, remove the main burner orifi ce. A
back-up wrench must be used on the manifold, located below the
housing to ensure that the aluminium tubing does not twist or kink.
Replace the burner orifi ce supplied using pipe thread compound.
SIT
PILOT
HOOD
PILOT
INJECTOR
8. Replace and re-secure the burner assembly
and log support, ensuring that the venturi fi ts
over the burner orifi ce.
9. Remove the venturi access cover and
inspect to confi rm correct venturi-orifi ce
position.
10. To convert the main valve to the desired
fuel, follow the instructions that are supplied
with the SIT regulator assembly kit.
11. The conversion data label must be fi lled out and attached
adjacent to the valve.
12. Turn on the gas supply and check for gas leaks by brushing on a
soap and water solution.
Do not use open fl ame.
13. Replace the log set. Then light the pilot and main burner to ensure
that the gas lines have been purged.
14. Close the glass viewing door. Turn on the electrical supply to the
appliance.
Purge all gas lines with the glass door open.
Assure that a continuous fl ow is at the burner before closing
the door.
6. Remove the burner hood from the
pilot assembly by pulling vertically.
Use an allen key to unscrew the injector.
Replace the pilot injector with the one
supplied. Replace the pilot hood onto
the assembly ensuring key position for
proper alignment. The fl ame opening
on the hood must align with the
thermocouple and the thermopile.
7. Before replacing the burner
assembly, adjust the burner shutter
opening.
Continued on reverse
1
1
1
1
1

Advertisement

loading

Summary of Contents for Napoleon CONTINENTAL W175-0159

  • Page 1 INSTALLER: THESE INSTRUCTIONS ARE TO REMAIN WITH THE HOME OWNER. CHECK THE BOXES TO INDICATE THAT THE CORRESPONDING STEPS HAVE BEEN COMPLETED. FUEL CONVERSION FOR MODELS BGD36/BCDV36, BGD36CF/BCDV36CF, BGNV36/BCNV36 These kits are for use at altitudes of 0 to 4500 feet. W175-0159, Natural Gas to Propane W175-0164, Propane to Natural Gas (BGD/BCDV36/36CF) (BGD/BCDV36/36CF,BGNV/BCNV36)
  • Page 2 ADJUSTMENTS PILOT BURNER ADJUSTMENT VENTURI ADJUSTMENT All models have air shutters that have been factory set open PILOT according to the chart below: BURNER THERMOPILE These setting are for (maximum) horizontal termination. THERMOCOUPLE BGD/BCDV36 BGD/BCDV36CF BGNV/BCNV36 ” ” ” ” ”...
  • Page 3 INSTALLATEUR : CES INSTRUCTIONS DOIVENT ÊTRE GARDÉES PAR LE PROPRIÉTAIRE. VEUILLEZ COCHER LES CASES POUR INDIQUER QUE LES ÉTAPES CORRESPONDANTES ONT ÉTÉ COMPLÉTÉES. ENSEMBLE DE CONVERSION POUR LES MODÈLES BGD36/BCDV36, BGD36CF/BCDV36CF, BGNV36/BCNV36 Cet ensemble est utilisé pour des altitudes de 0 à 4 500 pieds. W175-0159, Gaz Naturel au Propane W175-0164, Propane au Gaz Naturel(BGD/BCDV36/36CF) (BGD/BCDV36/36CF,BGNV/BCNV36)
  • Page 4 RÉGLAGES RÉGLAGES DE LA VEILLEUSE RÉGLAGE DU VENTURI L’ouverture des volets d’air de chaque modèle a été VEILLEUSE THERMOPILE préréglée en usine selon le tableau ci-dessous : Ces réglages sont pour une course maximale avec THERMOCOUPLE terminaison horizontale. BGD/BCDV36 BGD/BCDV36CF BGNV/BCNV36 ”...

This manual is also suitable for:

Continental w175-0164Continental w175-0280