LG 100K Installation Manual page 21

Table of Contents

Advertisement

INSTALLATION GUIDE AT THE SEASIDE
CAUTION
!
• Air conditioners should not be installed
in areas where corrosive gases, such as
acid or alkaline gas, are produced.
• Do not install the product where it could
be exposed to sea wind (salty wind) di-
rectly. It can result corrosion on the
product. Corrosion, particularly on the
condenser and evaporator fins, could
cause product malfunction or inefficient
performance.
• If outdoor unit is installed close to the
seaside, it should avoid direct exposure
to the sea wind. Otherwise it needs ad-
ditional anticorrosion treatment on the
heat exchanger.
1
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close
to the seaside, direct exposure to the sea
wind should be avoided. Install the outdoor
unit on the opposite side of the sea wind
direction.
Sea wind
Sea wind
2
In case, to install the outdoor unit on the
seaside, set up a windbreak to prevent
oudoor unit from the sea wind.
INSTALLATION GUIDE AT THE SEASIDE
Windbreak
Sea wind
- It should be strong enough like concrete
to prevent the outdoor unit from the sea
wind.
- The height and width should be more
than 150% of the outdoor unit.
- It should be keep more than 70 cm of
space between outdoor unit and the
windbreak for easy air flow.
3
Place with fluent water draining
- Install at a place with fluent water drain-
ing to prevent damage from localized
heavy rain and avoid frequent flooded
area.
- If you can't meet above guide line in the
seaside installation, please contact LG
Electronics for the additional anticorro-
sion.
- Periodic ( more than once/year ) clean-
ing of the dust or salt particles stuck on
the heat exchanger by using water
21

Advertisement

Table of Contents
loading

This manual is also suitable for:

150k

Table of Contents