Additional Refrigerant Charge - LG 100K Installation Manual

Table of Contents

Advertisement

Additional Refrigerant Charge

R410 Line charge
Suction (inch)
1/2
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
2-1/8
2-5/8
* Charges are based upon 40 oF suction temperature and 105 oF liquid temperature oz in this
page is mass indicating (1 oz = 28.35g)
Additioanl charge = ( Total piping length - chargeless length ) x additional charge rate
Example : For a R22 system using 3/8 liquid line and a 3/4 suction line with total measured
length of feet and with chargeless length 15 feet,
- Liquid line (50-15 feet) x 0.62 oz/ft
- Suction line (50-15 feet) x 0.06 oz/ft
- Total additional charge for interconnecting pipe = 23.8 oz
NOTE
!
Chargeless length is depending on each OEM.
oz/ft
Liquid (inch)
0.04
0.06
0.09
0.12
0.2
0.31
0.43
0.76
1.17
INSTALLATION OF UNIT
1/4
5/16
3/8
1/2
5/8
3/4
7/8
1-1/8
= 21.7 oz
= 2.1 oz
13
oz/ft
0.19
0.33
0.51
1.01
1.64
2.46
3.27
5.58

Advertisement

Table of Contents
loading

This manual is also suitable for:

150k

Table of Contents