Note On Adding Refrigerant - Beko BEHPH 090 User Manual

Split type air conditioner
Table of Contents

Advertisement

Available languages

Available languages

6 Air evacuation

6.1.3 Note on adding refrigerant

Some systems require additional charging
depending on pipe lengths. The standard pipe
length varies according to local regulations. For
example, in North America, the standard pipe
Additional refrigerant per pipe length
Connective
Air
Pipe Length
Purging
(m)
Method
<
Vacuum
Standard
Pump
pipe length
>
Vacuum
Standard
Pump
pipe length
For R290 refrigerant unit, the total amount
of refrigerant to be charged is no more than:
387g (<=9000Btu/h), 447g (>9000Btu/h and
<=12000Btu/h),
547g
<=18000Btu/h),
632g
<=24000Btu/h).
A
CAUTION!
refrigerant types.
40 / 172 EN
Liquid Side: Ø 6.35 (ø 0.25")
R32:
(Pipe length – standard length) x 12g/m
(Pipe length – standard length) x 0.13oZ/ft
R290:
(Pipe length – standard length) x 10g/m
(Pipe length – standard length) x 0.10oZ/ft
R410A:
(Pipe length – standard length) x 15g/m
(Pipe length – standard length) x 0.16oZ/ft
R22:
(Pipe length – standard length) x 20g/m
(Pipe length – standard length) x 0.21oZ/ft
(>12000Btu/h
and
(>18000Btu/h
and
DO
NOT
mix
length is 7.5m (25'). In other areas, the standard
pipe length is 5m (16'). The refrigerant should be
charged from the service port on the outdoor unit's
low pressure valve. The additional refrigerant to
be charged can be calculated using the following
formula:
Additional Refrigerant
N/A
Liquid Side: Ø 9.52 (ø 0.375")
(Pipe length – standard length) x 24g/m
(Pipe length – standard length) x 0.26oZ/ft
(Pipe length – standard length) x 18g/m
(Pipe length – standard length) x 0.19oZ/ft
(Pipe length – standard length) x 30g/m
(Pipe length – standard length) x 0.32oZ/ft
(Pipe length – standard length) x 40g/m
(Pipe length – standard length) x 0.42oZ/ft
Split Type Air Conditioner / User Manual
R32:
R410A:
R22:

Hide quick links: