Summary of Contents for RKI Instruments 65-2405RK-05
Page 1
65-2405RK-05 Combustible Gas Transmitter Operator’s Manual Part Number: 71-0180RK Revision: 0 Released: 2/16/11 1.800.561.8187 information@itm.com www. .com...
Page 2
Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage. 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www.
Page 3
Product Warranty RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge.
WARNING: When using the 65-2405RK-05, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 65-2405RK-05 and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 65-2405RK-05 as described in this manual.
The flame arrestor guard protects the flame arrestor from impact damage. Four color-coded leads extend from the top of the detector. The leads allow you to connect the detector to the amplifier. 2 • 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www.
Consult RKI Instruments, Inc. if you plan to change the calibration gas for the transmitter, for example from a methane calibration to a hexane calibration. The amplifier includes the detector terminal strip, controller terminal strip, span pot, zero pot, and test points (see Figure 1).
Reducing Bushing LEL Detector Figure 2: Mounting the Combustible Gas Transmitter At the monitoring site you select, hang or mount the junction box with the detector facing down (see Figure 2). 4 • 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www. .com...
The power cable may disrupt the transmission of the transmitter signal to the controller. 11. Connect the wires to the applicable detector/transmitter terminal strip at the controller as shown in Figure 3. 65-2405RK-05 Combustible Gas Transmitter • 5 1.800.561.8187 information@itm.com www.
Page 10
12. If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at the controller. RKI controllers typically have a ground stud that can be used to ground the cable’s drain wire. 6 • 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www.
If necessary, use a small flat-blade screwdriver to adjust the zero pot until the voltmeter reading is 100 mV (±2 mV). Remove the voltmeter leads from the test points. Secure the junction box cover to the junction box. 65-2405RK-05 Combustible Gas Transmitter • 7 1.800.561.8187 information@itm.com www.
Set a voltmeter to read in the millivolt (mV) range. Plug the voltmeter leads into the test points on the amplifier. Plug the positive lead into the red (+) test point; plug the negative lead into the black (-) test point. 8 • 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www.
NOTE: This troubleshooting guide describes transmitter problems only. See the controller operator’s manual for problems you may encounter with the controller. 65-2405RK-05 Combustible Gas Transmitter • 9 1.800.561.8187 information@itm.com www.
If necessary for environmental conditions, apply thread sealant or teflon tape to the hub and/or detector threads to seal them. 10 • 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www.
Page 15
Install the detector and controller terminal strips into their sockets on the new amplifier as shown in Figure 3 on page 6 of this manual. If controller leads or detector leads were removed during this procedure, refer to Table 4 and Table 5 below. 65-2405RK-05 Combustible Gas Transmitter • 11 1.800.561.8187 information@itm.com www.
3 to 6 months is adequate for most combustible gas transmitter applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months. If an application is not very demanding, for example detection in a clean, temperature...
Screw the regulator into the zero air calibration cylinder. Use the calibration kit sample tubing to connect the regulator to the calibration cup. Turn the regulator’s on/off knob counterclockwise to open the regulator. 65-2405RK-05 Combustible Gas Transmitter • 13 1.800.561.8187 information@itm.com www.
When the controller display reading falls below the alarm setpoints, return the controller to normal operation. Verify that the controller display reading decreases and stabilizes at 0 %LEL. Store the components of the calibration kit in a safe and convenient place. 14 • 65-2405RK-05 Combustible Gas Transmitter 1.800.561.8187 information@itm.com www.
Need help?
Do you have a question about the 65-2405RK-05 and is the answer not in the manual?
Questions and answers