Industrial Electronic Devices
Example:
0x68 - Start Byte
0xBD - L Fied
0xBD - L Field
0x68 - Start Byte
0x08 - C Field
0x02 - A Field
0x72 - CI Field
0x71 - Identification Number (Byte 4of4)
0x65 - Identification Number (Byte 3of4)
0x45 - Identification Number (Byte 2of4)
0x28 - Identification Number (Byte 1of4)
0x4D - Manufacturer (Byte 2of2)
0x6A - Manufacturer (Byte 1of2)
0x81 - Version
0x04 - Medium
0x3E - Access Number
0x27 - Status
0x00 - Signature (Byte 2of2)
0x00 - Signature (Byte 1of2)
0x04 - DIF
0x79 - VIF
Identification
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)
0x04 - DIF
0x06 - VIF
Energy
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)
0x44 - DIF
0x06 - VIF
Energy
0x00 - Data (Byte 4Of4)
0x00 - Data (Byte 3Of4)
0x00 - Data (Byte 2Of4)
0x00 - Data (Byte 1Of4)
...
...
Other Variables
...
0x55 - Check Sum
0x16 - Stop Byte
ADFweb.com S.r.l.
Fixed Data Header
First Variable ( 1 )
Second Variable ( 2 )
Third Variable ( 3 )
User Manual M-Bus / M-Bus Wireless / MQTT
Document code: MN67931_ENG
To be use in the "Position" field
Revision 1.000
Page 30 of 46
Need help?
Do you have a question about the M-Bus and is the answer not in the manual?
Questions and answers