Switch Output Do Mode Setting; Device Address - Ebyte MA02-XACX0440 User Manual

Table of Contents

Advertisement

Chengdu Ebyte Electronic Technology Co.,Ltd.
User Manual
【4AI+4DO】MA02-XACX0440
(contact capacity) of 30V/10A or 250V/10A.
Each DO output is designed with an output indicator (red LED indication) to indicate whether the
output port is on or off. When the LED indicator is on, it means the relay is closed (normally open on,
normally closed off); when the LED indicator is off, it means the relay is not closed (normally open
off, normally closed on).
Figure 4-2-1 Switch output DO interface

4.2.2 Switch output DO mode setting

(1) Level mode
Output according to the level set by the user. The switching characteristics of the level mode are
similar to the function of a self-locking switch.
(2) Pulse mode
After the switch output DO is turned on, the set pulse width time (in ms) is maintained, and the
switch output DO is automatically turned off. The pulse width setting range is 50~65535 (default
50).
(3) Follow mode
After the user sets the follow mode, set the follow input terminal. The switch output DO terminal is
consistent with the DI input terminal.
Note: Multiple switch output DO terminals can be set to follow one DI input terminal, and one
switch output DO terminal can not be set to follow multiple DI input terminals.

4.3 Device address

4.3.1 Device address

Device address composition: hardware address + software offset address
17
Copyright ©2012–2021,Chengdu Ebyte Electronic Technology Co.,Ltd.